Title: Integrating Liquid-to-Air Sidecars in High-Power Data Centers: Challenges and Best Practices
Abstract The rapid growth of AI workloads has pushed rack power densities to unprecedented levels, testing the limits of legacy air-cooled data centers. Liquid-to-air (L2A) sidecar coolant distribution units (CDUs) have emerged as a practical, cost-effective solution for enabling rack deployments exceeding 125 kW without requiring major infrastructure changes. However, their scalability and reliability in real-world environments remain constrained by operational challenges such as air leakage, flow sensor drift, fan speed oscillations, and delayed redundancy activation. To address these limitations, we conducted a systematic experimental investigation of L2A CDU performance under high-load conditions. Our testing demonstrated the reliability risks associated with these limitations. Air leakage induced supply air temperature (SAT) variations from 20.9 °C to 27.6 °C, while pump failover delays of approximately 10 s resulted in transient case temperature spikes exceeding 130 °C. To mitigate these risks, we implemented and validated targeted solutions, including ultrasonic flow sensing, predictive fan control algorithms, and dual-active pump configurations. Ultimately, these results provide a practical roadmap for reducing deployment risks and improving system resilience. As AI data centers continue to scale toward megawatt-class rack power levels, this work highlights the critical factors necessary for a safe transition from hybrid cooling to next-generation, liquid-focused thermal architectures.  more » « less
Award ID(s):
2209776
PAR ID:
10704493
Author(s) / Creator(s):
; ; ; ; ; ;
Publisher / Repository:
ASME
Date Published:
Journal Name:
Journal of Electronic Packaging
Volume:
148
Issue:
4
ISSN:
1043-7398
Subject(s) / Keyword(s):
liquid cooling, L2A CDU, failure modes
Sponsoring Org:
National Science Foundation
More Like this
  1. The rapid growth in data center workloads and the increasing complexity of modern applications have led to significant contradictions between computational performance and thermal management. Traditional air-cooling systems, while widely adopted, are reaching their limits in handling the rising thermal footprints and higher rack power densities of next-generation servers, often resulting in thermal throttling and decreased efficiency, emphasizing the need for more efficient cooling solutions. Direct-to-chip liquid cooling with cold plates has emerged as a promising solution, providing efficient heat dissipation for high-performance servers. However, challenges remain, such as ensuring system stability under varying thermal loads and optimizing integration with existing infrastructure. This comprehensive study digs into the area of data center liquid cooling, providing a novel, comprehensive experimental investigation of the critical steps and tests necessary for commissioning coolant distribution units (CDUs) in direct-to-chip liquid-cooled data centers. It carefully investigates the hydraulic, thermal, and energy aspects, establishing the groundwork for Liquid-to-Air (L2A) CDU data centers. A CDU’s performance was evaluated under different conditions. First, the CDU’s maximum cooling capacity was evaluated and found to be as high as 89.9 kW at an approach temperature difference (ATD) of 18.3 ◦C with a 0.83 heat exchanger effectiveness. Then, to assess the cooling performance and stability of the CDU, a low-power test and a transient thermohydraulic test were conducted. The results showed instability in the supply fluid temperature (SFT) caused by the oscillation in fan speed at low thermal loads. Despite this, heat removal rates remained constant across varying supply air temperatures (SATs), and a partial power usage effectiveness (PPUE) of 1.042 was achieved at 100 % heat load (86 kW) under different SATs. This research sets a foundation for improving L2A CDU performance and offers practical insights for overcoming current cooling limitations in data centers. 
    more » « less
  2. As web-based AI applications are growing rapidly, server rooms face escalating computational demands, prompting enterprises to either upgrade their facilities or outsource to co-located sites. This growth strains conventional heating ventilation and air-conditioning (HVAC) systems, which struggle to handle the substantial thermal load, often resulting in hotspots. Liquid-to-air (L2A) coolant distribution units (CDUs) emerge as a solution, efficiently cooling servers by circulating liquid coolant through cooling loops (CLs) mounted on each server board. In this study, the performance of a 24-kW L2A CDU is evaluated across various scenarios, emphasizing cooling effect and stability. Experimental tests involve a rack with three thermal test vehicles (TTVs), monitoring both liquid coolant and air sides for analysis. Tests are conducted in a limited air-conditioned environment, resembling upgraded server rooms with conventional AC systems. The study also assesses the impact of high-power density cooling units on the server room environment, measuring noise, air velocity, and ambient temperature against ASHRAE standards for human comfort. Recommendations for optimal practices and potential system improvements are included in the research, addressing the growing need for efficient cooling solutions amidst escalating computational demands. 
    more » « less
  3. Abstract The next radical change in the thermal management of data centers is to shift from conventional cooling methods like air-cooling to direct liquid cooling to enable high thermal mass and corresponding superior cooling. There has been in the past few years a limited adoption of direct liquid cooling in data centers because of its simplicity and high heat dissipation capacity. Single-phase engineered fluid immersion cooling has several other benefits like better server performance, even temperature profile, and higher rack densities and the ability to cool all components in a server without the need for electrical isolation. The reliability aspect of such cooling technology has not been well addressed in the open literature. This paper presents the performance of a fully single-phase dielectric fluid immersed server over wide temperature ranges in an environmental chamber. The server was placed in an environmental chamber and applied extreme temperatures ranging from −20 °C to 10 °C at 100% relative humidity and from 20 to 55 °C at constant 50% relative humidity for extended durations. This work is a first attempt of measuring the performance of a server and other components like pump including flow rate drop, starting trouble, and other potential issues under extreme climatic conditions for a completely liquid-submerged system. Pumping power consumption is directly proportional to the operating cost of a data center. The experiment was carried out until the core temperature reached the maximum junction temperature. This experiment helps to determine the threshold capacity and the robustness of the server for its applications in extreme climatic conditions. 
    more » « less
  4. As the online frameworks and services are growing rapidly with the evolution of web-based Artificial Intelligence (AI) applications, server rooms are upgrading in computational capacity and size to keep up with these demands. Enterprise companies with their limited capacity server rooms struggle to keep up with these increasing computational demands. Hence, some of them end up outsourcing their servers to co-located facilities (Co-Lo) and the others choose to upgrade their existing server rooms. Correspondingly, the thermal load associated with such upgrades is typically tremendous. Approximately around 40% of the power consumed by datacentres is dissipated as heat. Conventional HVAC systems fail to satisfy the requirements of such server capacities. Not only do they struggle to fulfil the cooling load, but their maldistribution of cool air into the server room forms a major cause for hotspots formation. To tackle this issue, Liquid-to-Air (L2A) Coolant Distribution Units (CDUs) are being used as a liquid-based cooling solution for rack-level cooling. This type of CDUs provide efficient cooling for servers through liquid coolant that is distributed into cooling loops mounted on top of each server board. The generated heat is curried away using this liquid coolant back to the CDU, which then dissipates it into the surrounding air using dedicated pumps, fans, and heat exchanger, hence the name Liquid-to-Air. In the present work, one of the most popular liquid cooling strategies is explored based on various scenarios. the performance of a 24-kW liquid to Air (L2A) CDU is judged based on cooling effect, stability, and reliability. The study is curried out experimentally, in which a test rack with three thermal test vehicles (TTVs) are used to investigate various operation scenarios. Both liquid coolant and air sides of this experimental setup are equipped with the required instrumentations to monitor and analyse the tests. All test cases were taken in a room with limited air conditioning to resemble the environment of upgraded server rooms with conventional AC systems. Moreover, the impact of using such high-power density cooling unit on the server room environment with restricted HVAC system is also brought to light. Environmental and human comfort parameters such as noise, air velocity, and ambient temperature are measured under various operation conditions and benchmarked against their ranges for human comfort as listed in ASHREE standards. At the end of this research, recommendations for best practice are provided along with areas of enhancement for the selected system. 
    more » « less
  5. There are various designs for segregating hot and cold air in data centers such as cold aisle containment (CAC), hot aisle containment (HAC), and chimney exhaust rack. These containment systems have different characteristics and impose various conditions on the information technology equipment (ITE). One common issue in HAC systems is the pressure buildup inside the HAC (known as backpressure). Backpressure also can be present in CAC systems in case of airflow imbalances. Hot air recirculation, limited cooling airflow rate in servers, and reversed flow through ITE with weaker fan systems (e.g. network switches) are some known consequences of backpressure. Currently there is a lack of experimental data on the interdependency between overall performance of ITE and its internal design when a backpressure is imposed on ITE. In this paper, three commercial 2-rack unit (RU) servers with different internal designs from various generations and performance levels are tested and analyzed under various environmental conditions. Smoke tests and thermal imaging are implemented to study the airflow patterns inside the tested equipment. In addition, the impact leak of hot air into ITE on the fan speed and the power consumption of ITE is studied. Furthermore, the cause of the discrepancy between measured inlet temperatures by internal intelligent platform management interface (IPMI) and external sensors is investigated. It is found that arrangement of fans, segregation of space upstream and downstream of fans, leakage paths, location of sensors of baseboard management controller (BMC) and presence of backpressure can have a significant impact on ITE power and cooling efficiency. 
    more » « less