Title: Dataset of subatmospheric pool boiling of water on copper surfaces
Abstract: This dataset contains 30 transient saturated pool-boiling experiments with deionized water on flat copper, straight-microchannel copper, and square-micropillar copper surfaces at nominal vapor-space pressures of 10, 20, 30, 40, 50, 60, 70, 80, 90, and 100 kPa. One transient is provided for each surface-pressure combination. In each standard test, a single electrical-heating step was applied until a CHF-related thermal excursion was identified, after which the heater was turned off and the cooling/recovery response was recorded. The archive includes native thermocouple and pressure records, processed thermal histories, reconstructed surface temperature, heat flux, wall superheat, heat-transfer coefficient, selected boiling-event fields, side-view high-speed videos, NumPy data archives, and selected image-derived BubbleID quantities. The data support analysis of CHF, post-CHF recovery, boiling hysteresis, thermal history, pressure effects, and surface-structure effects. The boiling-hysteresis ratio used in the companion manuscript is $$H=q''_{NBR}/q''_{CHF}$$, where NBR denotes the sustained return to the nucleate-boiling branch. Reconstructed thermal quantities and event labels are derived outputs, while projected vapor fraction and bubble counts are side-view image metrics rather than volumetric void fraction or wall dry-area measurements. The dataset is not a replicated performance database and should be analyzed with condition-aware methods because pressure sequence, surface history, and run order were not fully randomized. The companion analysis and figure-generation workflow is available in BoilingLab (https://github.com/UARK-NED3/BoilingLab/tree/main/manuscripts/boiling_hysteresis_subatmospheric).  more » « less
Award ID(s):
2323022
PAR ID:
10712572
Author(s) / Creator(s):
; ; ; ;
Publisher / Repository:
Zenodo
Date Published:
Subject(s) / Keyword(s):
Right(s):
Creative Commons Attribution 4.0 International
Sponsoring Org:
National Science Foundation
More Like this
  1. Abstract: The ned3-019-BoilingHysteresis10kPa dataset contains five extended-heating saturated pool-boiling experiments on a flat copper surface at approximately 10 kPa and 60 W. Unlike the 30 standard tests, in which the heater was turned off shortly after CHF detection, these experiments intentionally prolonged heating after CHF to produce progressively higher post-CHF maximum surface temperatures, from approximately 75.6 to 250.1 °C. Each case includes native and processed thermal and pressure measurements, reconstructed heat-flux and surface-temperature histories, high-speed side-view video, hydrophone signals, acoustic-emission data, synchronization metadata, and derived plots. The dataset was developed to examine how post-CHF thermal history affects the return to nucleate boiling and boiling hysteresis, and serves as an external protocol-validation dataset rather than an independent set of fitting cases. This dataset is the five-case protocol-perturbation dataset used to test the boiling-hysteresis correlation in: *Pressure-Adjusted Post-CHF Apparent Base-Wall Superheat Correlates with Boiling Hysteresis in Subatmospheric Pool Boiling.* The dataset has DOI [10.5281/zenodo.22235808](https://doi.org/10.5281/zenodo.22235808) and is released under the [Creative Commons Attribution 4.0 International license](https://creativecommons.org/licenses/by/4.0/). The companion 30-case standard dataset is stored separately in `ned3-013_SubatmosphericBoiling`. The standard cases use one transient for each of three copper surfaces and ten nominal pressures. The present five cases use flat copper at approximately 10 kPa and intentionally extend the heating period after the CHF indication to produce different post-CHF maximum wall temperatures. They were excluded from fitting and used only as withheld protocol-validation cases. ## Cases and experimental design | Directory | Case identifier in raw/plot filenames | Nominal condition | Measured maximum surface temperature | |---|---|---|---:| | `1-Tmax_at_CHF` | `Boiling-420` | baseline; approximately 10 kPa; 60 W | 75.6 degC | | `2_Tmax_100C` | `Boiling-421` | approximately 100 degC target; approximately 10 kPa; 60 W | 101.7 degC | | `3_Tmax_150C` | `Boiling-422` | approximately 150 degC target; approximately 10 kPa; 60 W | 150.5 degC | | `4_Tmax_200C` | `Boiling-423` | approximately 200 degC target; approximately 10 kPa; 60 W | 198.7 degC | | `5_Tmax_250C` | `Boiling-424` | approximately 250 degC target; approximately 10 kPa; 60 W | 250.1 degC | The temperatures in the last column are derived values read from the retained processed summaries. The target temperature and the measured maximum temperature are not identical for every case. Use the measured value for quantitative analysis. 
    more » « less
  2. The growing power density of microelectronics has intensified the demand for high-performance cooling solutions. Subatmospheric pool boiling of water offers a promising pathway to extend the use of water-based cooling by reducing saturation temperature. However, reduced critical heat flux (CHF) and heat transfer coefficient (HTC) at low pressures remain key challenges. In this work, we experimentally investigate the coupled effects of pressure and surface structures on pool boiling performance and boiling hysteresis. Transient pool boiling experiments were conducted on flat copper, copper microchannel, and copper micro-pin-fin surfaces over a pressure range of 10 – 100 kPa. The results show that both CHF and HTC increase monotonically with pressure for all surfaces, while surface structures consistently enhance boiling performance across the entire pressure range. Distinct roles of pressure-structure coupling are identified in CHF and HTC. CHF is predominantly governed by surface structures, with structured surfaces at 10 kPa exhibiting higher CHF than a flat surface at atmospheric pressure. In contrast, HTC is influenced by both pressure and surface structure, with notable overlap between their effects. In addition, CHF-induced boiling hysteresis is substantially mitigated at low pressures (10 – 30 kPa), which leads to rapid recovery to nucleate boiling with minimal overheating. These findings demonstrate that the degradation of boiling performance at subatmospheric pressures can be effectively mitigated through surface engineering and that the complementary roles of surface structures (passive control) and pressure (active control) promise decoupled and targeted control of CHF and HTC. The results provide new insight into pressure-structure coupling in pool boiling and support subatmospheric operation combined with surface microstructuring as a viable strategy for reliable, high-performance water-based cooling of high-power-density electronic systems. 
    more » « less
  3. Abstract Two-phase direct-to-chip cooling is emerging as an important thermal management pathway for the rapidly increasing thermal design powers of modern AI superchips while maintaining data center energy efficiency. This paper presents a combined passive–active approach that transitions high-performance saturated heterogeneous nucleate boiling to a stabilized and controlled flash-nucleate boiling regime using low-power piezoelectric actuation that produces feather-like in-plane and out-of-plane microvibrations of the heated surface. Experiments on microstructured copper cold plates (CPs) with dielectric fluids, at 100–140 kPa pressures, establish baseline enhanced nucleate boiling (ENB-1) performance in partial flow-boiling configurations typical of direct-to-chip flow loops. These results quantify cold-plate behavior and indicate that physics-guided modifications of the experimentally tested microstructures and flow-loop design, as modeled and proposed for further experimental testing, can substantially increase heat-transfer coefficients and critical heat flux (CHF). Activation of megahertz piezo-actuators with low-frequency modulation near antiresonance generates small microvibrations that modify nucleating bubble dynamics and their characteristic frequencies. This triggers a rapid transition to a controlled, stabilized high-pressure (400–500 kPa) heterogeneous flash-nucleate boiling regime (ENB-2), sustained at the boiling surface by “on–off” microlayer heating and acoustic streaming mechanisms. This transition from ENB-1 to ENB-2 accompanies a short-duration (tens of milliseconds) increase in interfacial mass transfer across bubble microlayers, producing transient heat extraction of 200–400 J from underneath the heated surface, that is, from the chip to the ENB-2 condenser with a sustained high pressure at the vapor exit of the cold plate. Three-dimensional transient conduction simulations predict chip-level temperature reductions of about 15–20 °C for low-thermal-inertia test vehicles and future chip implementations. Baseline experiments show nucleate boiling heat transfer with critical heat flux near 50–60 W/cm2 and a lower heat-transfer coefficient (HTC) of 1–2 W/cm2 °C. The tested and deployed architecture is amenable to further optimization to higher CHF (135–175 W/cm2 or more) and associated HTC (up to 150 W/cm2 °C) for ENB-1 and 10–20 °C cooler chips through ENB-2. Observed ENB-2 condenser performance suggests a shift from the ENB-1 condenser to a direct-contact tank/pool condenser for ENB-2, which would allow sustained waste-heat recovery from the vapor at, say, 70 °C and 400 kPa. That is, a stabilized flash-boiling regime supports lower junction temperatures, improved chip reliability, and more energy-efficient next-generation AI data centers. 
    more » « less
  4. Abstract The increasing trend of power densities in high-performance computing, driven by artificial intelligence, machine learning, and cloud computing, necessitates advanced thermal management solutions to maintain operational stability and energy efficiency. This study examines the effectiveness of cooling a 1.5 U simulated copper microchannel chip compared to a plain chip. Both chip types were tested with and without configurations for dual taper microgaps to enhance the heat transfer performance of a boiling chamber (BC). Experimental investigation was conducted using 500 μm wide × 400 μm deep microchannels separated by 200 μm fins. Varying inlet gaps (0.5–4 mm) and taper lengths (8.25 mm and 16.5 mm) with a taper angle of 3 deg were employed in dual taper configuration. Their impact on critical heat flux (CHF) and subcooled boiling dynamics was investigated. Microchannels provided considerable performance enhancement over a plain surface with or without the dual taper microgap. The findings demonstrate that smaller inlet gaps (0.5–1 mm) and longer taper lengths (16.5 mm, with central liquid inlet) significantly enhance nucleate boiling. These configurations improve vapor escape and delay CHF through subcooled boiling and submerged condensation. However, a lower CHF was noted due to vapor agglomeration within the microgap. The 80% fill ratio microchannel chip exhibited the highest CHF as subcooled boiling increased liquid replenishment and prevented vapor stagnation. Similarly, lower coolant temperatures (20–30 °C) enhanced boiling performance, where submerged condensation accelerated bubble collapse and improved heat dissipation efficiency in lower surface temperatures. 
    more » « less
  5. Abstract This work presents the experimental characterization of pool boiling heat transfer enhancement on cylindrical tubes with circumferential micro-channels using saturated water at atmospheric pressure as the working fluid. Three engineered copper tubes with 300 μm, 600 μm and 900 μm fin width and a fixed 400 μm channel width with 410 μm channel depth were machined using CNC. To compare the boiling enhancement on engineered tubes, one plain copper tube was used as the reference heater. The active heating area on the cylindrical tubes had a dimension of 9.5 mm outer diameter and 10.5 mm length. A custom-built cylindrical heater was designed using a nichrome wire coil of 30 AWG with a resistance of 19.57 Ω/inch of coil to provide joule heating to the cylindrical tubes. The electrical wire was insulated from the copper heater using a thin layer of alumina paste. The saturated pool boiling tests up to critical heat flux (CHF) were conducted at atmospheric pressure. While an approximate CHF of ∼70 W/cm2 was achieved for the plain copper tube, the cylindrical tube with microchannel geometry showed a CHF range of 131–144 W/cm2 that corresponds to 87%–100% enhancement as compared to plain cylindrical tube. 
    more » « less