Title: Performance Analysis of Liquid-to-Air Heat Exchanger of High-Power Density Racks
The ability of traditional room-conditioning systems to accommodate expanding information technology loads is limited in contemporary data centers (DCs), where the storage, storing, and processing of data have grown quickly as a result of evolving technological trends and rising demand for online services, which has led to an increase in the amount of waste heat generated by IT equipment. Through the implementation of hybrid air and liquid cooling technologies, targeted, on-demand cooling is made possible by employing a variety of techniques, which include but are not limited to in-row, overhead, and rear door heat exchanger (HX) cooling systems. One of the most common liquid cooling techniques will be examined in this study based on different conditions for high-power density racks (+50 kW). This paper investigates the cooling performance of a liquid-to-air in-row coolant distribution unit (CDU) in test racks containing seven thermal test vehicles (TTVs) under various conditions, focusing on cooling capacity and HX effectiveness under different supply air temperatures (SAT). This test rig has the necessary instruments to monitor and analyze the experiments on both the liquid coolant and the air sides. Moreover, another experiment is conducted to assess the performance of the CDU that runs under different control fan schemes, as well as how the change of the control type will affect the supply fluid temperature and the TTV case temperatures at 10%, 50%, and 100% of the total power. Finally, suggestions for the best control fan scheme to use for these systems and units are provided at the conclusion of the study.

 
more » « less
Award ID(s):
2209776
NSF-PAR ID:
10529824
Author(s) / Creator(s):
; ; ; ; ; ; ; ;
Publisher / Repository:
ASME
Date Published:
Journal Name:
Journal of Electronic Packaging
Volume:
146
Issue:
4
ISSN:
1043-7398
Subject(s) / Keyword(s):
data center high heat density rack liquid cooling liquid-to-air heat exchanger cold plate
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Owing to the dramatic increase in IT power density and energy consumption, the data center (DC) sector has started adopting thermally- and energy-efficient liquid cooling methods. This study examines a single-phase direct-to-chip liquid cooling approach for three high-heat-density racks, utilizing two liquid-to-air (L2A) cooled coolant distribution units (CDUs) and a combined total heat load of 128 kW. An experimental setup was developed to test different types of CDUs, cooling loops, and thermal testing vehicles (TTVs) for different operating conditions. IR images and the collected data were used to investigate the effect of air recirculation between cold and hot aisle containments on the CDU’s performance and stability of supply air temperature (SAT). Three different types of cooling loops (X, Y, and Z) were characterized thermally and hydraulically. Results show that Type Y has the lowest cold plate thermal resistance and pressure drop, among others. In a later test that included a single rack at a heat load of 53 kW and a single CDU, the heat capture ratio for fluid was found to be 94%. Experiments show that using blanking panels on the back of the racks limits hot air recirculation and maintains a steady SAT in the cold aisle. Finally, the CDU performance was evaluated at a high heat load for the three racks at 128 kW, and the average cooling capacity of the units is 58.6 kW, and the effectiveness values for CDU 1 and CDU 2 are 0.83 and 0.82, respectively. 
    more » « less
  2. As the demand for faster and more reliable data processing is increasing in our daily lives, the power consumption of electronics and, correspondingly, Data Centers (DCs), also increases. It has been estimated that about 40% of this DCs power consumption is merely consumed by the cooling systems. A responsive and efficient cooling system would not only save energy and space but would also protect electronic devices and help enhance their performance. Although air cooling offers a simple and convenient solution for Electronic Thermal Management (ETM), it lacks the capacity to overcome higher heat flux rates. Liquid cooling techniques, on the other hand, have gained high attention due to their potential in overcoming higher thermal loads generated by small chip sizes. In the present work, one of the most commonly used liquid cooling techniques is investigated based on various conditions. The performance of liquid-to-liquid heat exchange is studied under multi-leveled thermal loads. Coolant Supply Temperature (CST) stability and case temperature uniformity on the Thermal Test Vehicles (TTVs) are the target indicators of the system performance in this study. This study was carried out experimentally using a rack-mount Coolant Distribution Unit (CDU) attached to primary and secondary cooling loops in a multi-server rack. The effect of various selected control settings on the aforementioned indicators is presented. Results show that the most impactful PID parameter when it comes to fluctuation reduction is the integral (reset) coefficient (IC). It is also concluded that fluctuation with amplitudes lower than 1 ᵒC is converged into higher amplitudes 
    more » « less
  3. About 40% of the energy utilized in data centers is used for cooling systems, and this percentage has increased significantly in recent years. Data center server racks receive indirect cooling from computer room air conditioning units (CRACs) or computer room air handler units (CRAHs), and chilled air is sent to the racks through a raised floor plenum to cool the server room. This approach is inefficient because the server room has excessive cooling while the IT equipment has inadequate cooling. The data center industry has begun to use thermally and energy-efficient single-phase liquid cooling solutions as a result of the tremendous increase in IT power density and energy usage. One of the most popular liquid cooling systems will be examined in the current study, which is based on numerous circumstances. Under various secondary coolant conditions, the hydro-thermal performance of different liquid-to-air and liquid-to-liquid coolant distribution units (CDUs) will be assessed experimentally using multi-racks loaded with different numbers of thermal testing vehicles (TTVs), and the system response to any change in the flow will be examined by disconnecting and reconnecting the TTVs cooling loops in the multi-racks through different sequences of transient events. Moreover, a set of rules and guidelines will be established to commission these units. 
    more » « less
  4. As the online frameworks and services are growing rapidly with the evolution of web-based Artificial Intelligence (AI) applications, server rooms are upgrading in computational capacity and size to keep up with these demands. Enterprise companies with their limited capacity server rooms struggle to keep up with these increasing computational demands. Hence, some of them end up outsourcing their servers to co-located facilities (Co-Lo) and the others choose to upgrade their existing server rooms. Correspondingly, the thermal load associated with such upgrades is typically tremendous. Approximately around 40% of the power consumed by datacentres is dissipated as heat. Conventional HVAC systems fail to satisfy the requirements of such server capacities. Not only do they struggle to fulfil the cooling load, but their maldistribution of cool air into the server room forms a major cause for hotspots formation. To tackle this issue, Liquid-to-Air (L2A) Coolant Distribution Units (CDUs) are being used as a liquid-based cooling solution for rack-level cooling. This type of CDUs provide efficient cooling for servers through liquid coolant that is distributed into cooling loops mounted on top of each server board. The generated heat is curried away using this liquid coolant back to the CDU, which then dissipates it into the surrounding air using dedicated pumps, fans, and heat exchanger, hence the name Liquid-to-Air.

    In the present work, one of the most popular liquid cooling strategies is explored based on various scenarios. the performance of a 24-kW liquid to Air (L2A) CDU is judged based on cooling effect, stability, and reliability. The study is curried out experimentally, in which a test rack with three thermal test vehicles (TTVs) are used to investigate various operation scenarios. Both liquid coolant and air sides of this experimental setup are equipped with the required instrumentations to monitor and analyse the tests. All test cases were taken in a room with limited air conditioning to resemble the environment of upgraded server rooms with conventional AC systems. Moreover, the impact of using such high-power density cooling unit on the server room environment with restricted HVAC system is also brought to light. Environmental and human comfort parameters such as noise, air velocity, and ambient temperature are measured under various operation conditions and benchmarked against their ranges for human comfort as listed in ASHREE standards. At the end of this research, recommendations for best practice are provided along with areas of enhancement for the selected system.

     
    more » « less
  5. Data Center hybrid air/liquid cooling systems such as rear door heat exchangers, overhead and in row cooling systems enable localized, on-demand cooling, or “smart cooling.” At the heart of all hybrid cooling systems is an air to liquid cross flow heat exchanger that regulates the amount of cooling delivered by the system by modulating the liquid or air flows and/or temperatures. Due the central role that the heat exchanger plays in the system response, understanding the transient response of the heat exchanger is crucial for the precise control of hybrid cooling system. This paper reports on the transient experimental characterization of heat exchangers used in data centers applications. An experimental rig designed to introduce controlled transient perturbations in temperature and flow on the inlet air and liquid flow streams of a 12 in. × 12 in. heat exchanger test core is discussed. The conditioned air is delivered to the test core by a suction wind tunnel with upstream air heaters and a frequency variable axial blower to allow the control of air flow rate and bulk temperature. The conditioned water is delivered to the test core by a water delivery system consisting of two separate water circuits, one delivering cold water, and the other hot water. By switching from one circuit to the other or mixing water from both circuits, the rig is capable of generating step, ramp and frequency perturbations in water temperature at constant flow or step, ramp or frequency perturbations in water flow at constant temperature or combinations of temperature and water flow perturbations. Experimental data are presented for a 12×12 heat exchanger core with a single liquid pass under different transient perturbations 