Title: Development of a Thermal Metrology Standard for Evaluation of Cold Plate Thermal Resistance as a Performance Metric
Abstract

A significant number of investigations have been performed to develop and optimize cold plates for direct-to-chip cooling of processor packages. Many investigations have reported computational simulations using commercially available computational fluid dynamic tools that are compared to experimental data. Generally, the simulations and experimental data are in qualitative agreement but often not in quantitative agreement. Frequently, the experimental characterizations have high experimental uncertainty. In this study, extensive experimental evaluations are used to demonstrate the errors in experimental thermal measurements and the experimental artifacts during testing that lead to unacceptable inconsistency and uncertainty in the reported thermal resistance. By comparing experimental thermal data, such as the temperature at multiple positions on the processor lid, and using that data to extract a meaningful measure of thermal resistance, it is shown that the data uncertainty and inconsistency are primarily due to three factors: (1) inconsistency in the thermal boundary condition supplied by the thermal test vehicle (TTV) to the cold plate, (2) errors in the measurement and interpretation of the surface temperature of a solid surface, such as the heated lid surface, and (3) errors introduced by improper contact between cold plate and TTV. A standard thermal test vehicle (STTV) was engineered and used to provide reproducible thermal boundary conditions to the cold plate. An uncertainty analysis was performed in order to discriminate between the sources of inconsistencies in the reporting of thermal resistance, including parameters such as mechanical load distribution, methods for measuring the cold plate base, and TTV surface temperatures. A critical analysis of the classical thermal resistance definition was performed to emphasize its shortcomings for evaluating the performance of a cold plate. It is shown that the thermal resistance of cold plates based on heat exchanger theory better captures the physics of the heat transfer process when cold plates operate at high thermodynamic effectiveness.

 
more » « less
Award ID(s):
2209691
PAR ID:
10537555
Author(s) / Creator(s):
; ;
Publisher / Repository:
ASME
Date Published:
Journal Name:
Journal of Electronic Packaging
Volume:
146
Issue:
4
ISSN:
1043-7398
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Effective cooling is crucial for high-power liquid-cooled servers to ensure optimal performance and reliability ofcomponents. Thermal characterization is necessary to ensure that the cooling system functions as intended, is energy efficient, and minimizes downtime. In this study, a proposed methodology for thermal characterization of a high-powerliquid-cooled server/TTV [server and TTVs (thermal test vehicle) are used interchangeably] is presented. The server layout includes multiple thermal test vehicle setups equipped with direct-to-chip cold plates, with two or more connected in series to form a TTV cooling loop. These cooling loops are connected in parallel to the supply and return plenums of the cooling loop manifold, which includes a chassis-level flow distribution manifold. To obtain accurate measurements, two identical server/TTV prototypes are instrumented with sensors for coolant flow rate and temperature measurements for every TTV cooling loop. Four ultrasonic flow sensors are installed in the flow verification server/TTV to measure the coolant flow rate to each TTV cooling loop. In the thermal verification server, thermistors are installed at the outlet of each GPU heater of TTV cooling loop to log temperature measurements. The amount of heat captured by the coolant in each TTV cooling loop is subsequently estimated based on the flow rates determined from the flow verification server.This methodology enables precise characterization of the thermal performance of high-power liquid-cooled servers,ensuring optimal functionality, energy efficiency, and minimized downtime.

     
    more » « less
  2. More than ever before, data centers must deploy robust thermal solutions to adequately host the high-density and high-performance computing that is in high demand. The newer generation of central processing units (CPUs) and graphics processing units (GPUs) has substantially higher thermal power densities than previous generations. In recent years, more data centers rely on liquid cooling for the high-heat processors inside the servers and air cooling for the remaining low-heat information technology equipment. This hybrid cooling approach creates a smaller and more efficient data center. The deployment of direct-to-chip cold plate liquid cooling is one of the mainstream approaches to providing concentrated cooling to targeted processors. In this study, a processor-level experimental setup was developed to evaluate the cooling performance of a novel computer numerical control (CNC) machined nickel-plated impinging cold plate on a 1 in.  1 in. mock heater that represents a functional processing unit. The pressure drop and thermal resistance performance curves of the electroless nickel-plated cold plate are compared to those of a pure copper cold plate. A temperature uniformity analysis is done using compuational fluid dynamics and compared to the actual test data. Finally, the CNC machined pure copper one is compared to other reported cold plates to demonstrate its superiority of the design with respect to the cooling performance. 
    more » « less
  3. Abstract

    In recent years there has been a phenomenal development in cloud computing, networking, virtualization, and storage, which has increased the demand for high performance data centers. The demand for higher CPU (Central Processing Unit) performance and increasing Thermal Design Power (TDP) trends in the industry needs advanced methods of cooling systems that offer high heat transfer capabilities. Maintaining the CPU temperature within the specified limitation with air-cooled servers becomes a challenge after a certain TDP threshold. Among the equipments used in data centers, energy consumption of a cooling system is significantly large and is typically estimated to be over 40% of the total energy consumed. Advancements in Dual In-line Memory Modules (DIMMs) and the CPU compatibility led to overall higher server power consumption. Recent trends show DIMMs consume up to or above 20W each and each CPU can support up to 12 DIMM channels. Therefore, in a data center where high-power dense compute systems are packed together, it demands efficient cooling for the overall server components. In single-phase immersion cooling technology, electronic components or servers are typically submerged in a thermally conductive dielectric fluid allowing it to dissipate heat from all the electronics. The broader focus of this research is to investigate the heat transfer and flow behavior in a 1U air cooled spread core configuration server with heat sinks compared to cold plates attached in series in an immersion environment. Cold plates have extremely low thermal resistance compared to standard air cooled heatsinks. Generally, immersion fluids are dielectric, and fluids used in cold plates are electrically conductive which exposes several problems. In this study, we focus only on understanding the thermal and flow behavior, but it is important to address the challenges associated with it. The coolant used for cold plate is 25% Propylene Glycol water mixture and the fluid used in the tank is a commercially available synthetic dielectric fluid EC-100. A Computational Fluid Dynamics (CFD) model is built in such a way that only the CPUs are cooled using cold plates and the auxiliary electronic components are cooled by the immersion fluid. A baseline CFD model using an air-cooled server with heat sinks is compared to the immersion cold server with cold plates attached to the CPU. The server model has a compact model for cold plate representing thermal resistance and pressure drop. Results of the study discuss the impact on CPU temperatures for various fluid inlet conditions and predict the cooling capability of the integrated cold plate in immersion environment.

     
    more » « less
  4. Abstract

    Impingement split flow liquid-cooled microchannel cold plates are one of several flow configurations used for single-phase liquid cooling. Split flow or top-in/side-exit (TISE) cold plates divide the flow into two branches thus resulting in halved or reduced flow rates and flow lengths, compared to traditional side-in /side-exit (SISE) or parallel flow cold plates. This has the effect of reducing the pressure drop because of the shorter flow length and lower flow rate and increasing the heat transfer coefficient due to thermally developing as opposed to fully developed flow. It is also claimed that the impinging flow increases the heat transfer coefficient on the base plate in the region of impingement. Because of the downward impinging and turning flow, there are no exact analytical models for this flow configuration. Computational and experimental studies have been performed, but there are no useful compact analytical models in the literature that can be used to predict the performance of these impingement cold plates. Results are presented for novel physics-based laminar flow models for a TISE microchannel cold plate based on an equivalent parallel channel flow approach. We show that the new models accurately predict the thermal-hydraulic performance over a wide range of parameters.

     
    more » « less
  5. Miniaturization and high heat flux of power electronic devices have posed a colossal challenge for adequate thermal management. Conventional air-cooling solutions are inadequate for high-performance electronics. Liquid cooling is an alternative solution thanks to the higher specific heat and latent heat associated with the coolants. Liquid-cooled cold plates are typically manufactured by different approaches such as: skived, forged, extrusion, electrical discharge machining. When researchers are facing challenges at creating complex geometries in small spaces, 3D-printing can be a solution. In this paper, a 3D-printed cold plate was designed and characterized with water coolant. The printed metal fin structures were strong enough to undergo pressure from the fluid flow even at high flow rates and small fin structures. A copper block with top surface area of 1 inch by 1 inch was used to mimic a computer chip. Experimental data has good match with a simulation model which was built using commercial software 6SigmaET. Effects of geometry parameters and operating parameters were investigated. Fin diameter was varied from 0.3 mm to 0.5 mm and fin height was maintained at 2 mm. A special manifold was designed to maximize the surface contact area between coolant and metal surface and therefore minimize thermal resistance. The flow rate was varied from 0.75 L/min to 2 L/min and coolant inlet temperature was varied from 25 to 48 oC. It was observed that for the coolant inlet temperature 25 oC and aluminum cold plate, the junction temperature was kept below 63.2 oC at input power 350 W and pressure drop did not exceed 23 Kpa. Effects of metal materials used in 3D-printing on the thermal performance of the cold plate were also studied in detail. 
    more » « less