Title: Pilot‐Scale Analysis of Stagnation and Flushing in Premise Plumbing
ABSTRACT Research has demonstrated that water quality degrades in commercial and institutional (C&I) building premise plumbing leading to increased risk to consumers. This study aimed to bridge the gap between real premise plumbing systems and theory by using a pilot scale pipe rig representative of C&I premise plumbing. The research examined changes in key water quality parameters, including chlorine, copper, trihalomethanes (THMs), and cellular ATP (cATP) across different flushing and stagnation conditions. Results indicated significant degradation during periods of stagnation found in real premise plumbing, with reductions in chlorine levels and increases in copper and THM concentrations. Conversely, flushing effectively renewed water quality, though the extent varied with system size and flow dynamics. Correlations were found between key water quality variables. The findings emphasize the need for strategic water management practices to mitigate risks associated with poor water quality in building plumbing systems.  more » « less
Award ID(s):
2027444
PAR ID:
10565337
Author(s) / Creator(s):
 ;  ;  
Publisher / Repository:
Wiley Blackwell (John Wiley & Sons)
Date Published:
Journal Name:
AWWA Water Science
Volume:
7
Issue:
1
ISSN:
2577-8161
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. null (Ed.)
    Flint, MI experienced two outbreaks of Legionnaires’ Disease (LD) during the summers of 2014 and 2015, coinciding with use of Flint River as a drinking water source without corrosion control. Using simulated distribution systems (SDSs) followed by stagnant simulated premise (i.e., building) plumbing reactors (SPPRs) containing cross-linked polyethylene (PEX) or copper pipe, we reproduced trends in water chemistry and Legionella proliferation observed in the field when Flint River versus Detroit water were used before, during, and after the outbreak. Specifically, due to high chlorine demand in the SDSs, SPPRs with treated Flint River water were chlorine deficient and had elevated L. pneumophila numbers in the PEX condition. SPPRs with Detroit water, which had lower chlorine demand and higher residual chlorine, lost all culturable L. pneumophila within two months. L. pneumophila also diminished more rapidly with time in Flint River SPPRs with copper pipe, presumably due to the bacteriostatic properties of elevated copper concentrations caused by lack of corrosion control and stagnation. This study confirms hypothesized mechanisms by which the switch in water chemistry, pipe materials, and different flow patterns in Flint premise plumbing may have contributed to observed LD outbreak patterns. 
    more » « less
  2. Extensive building closures due to the unprecedented COVID-19 pandemic resulted in long-term water stagnation within the plumbing of large buildings. This study examined water chemical quality deterioration in ten large buildings after prolonged stagnation caused by the closure of a university campus in response to the COVID-19 pandemic. Volume-based and constant-duration flushing protocols were implemented to replace stagnant water with fresh drinking water. The effectiveness of the developed water flushing protocols was examined by monitoring the disinfectant residuals, heavy metal concentrations and temperature for water samples collected from the buildings' point of entry (POE) and select water fixtures. More than 14 m 3 of water were flushed in all ten large buildings. The results demonstrated a significantly greater average total chlorine residual concentration in POE water samples collected after flushing (1.1 mg L −1 ) compared to the stagnant condition (0.6 mg L −1 ). For water samples collected from fixtures during the extended stagnation, chlorine was absent in 71% of samples from academic buildings and 69% of samples from athletic buildings. The effectiveness of flushing practices is underscored by increasing the median total chlorine concentration from <0.1 to 1.0 mg L −1 in academic buildings and from <0.1 to 0.75 mg L −1 in athletic buildings. Furthermore, the concentrations of Pb, Zn, and Cu had decreased following the water flushing, but the concentration of Fe had increased in some buildings. This study could be beneficial to prepare for prolonged water stagnation events including but not limited to pandemics. 
    more » « less
  3. Abstract Commercial and institutional buildings now experience weeks and even months with below‐normal occupancy due to remote work/learning, which results in reduced water use and has the potential to adversely impact water quality. This study monitored the variations in water quality in multiple university buildings during several months of below‐normal occupancy followed by several months of normal occupancy. The levels of free chlorine, copper, and cellular ATP in water varied within buildings and between buildings. Using Wi‐Fi activity as a surrogate for building occupancy, the free chlorine concentration in water increased as Wi‐Fi counts increased. The copper concentration in building water was higher when the occupancy was below‐normal compared with normal occupancy, and the copper concentration decreased as Wi‐Fi counts increased. Throughout the study, flushing a fixture at the time of use decreased the concentrations of copper and cellular ATP and increased the concentration of free chlorine. 
    more » « less
  4. Abstract Variable water quality within buildings is of increasing concern due to public health impacts (e.g., lead,Legionella pneumophila,Naegleria fowleri, disinfection byproducts). Advances in data acquisition and analytics provide the opportunity to monitor real‐time building‐wide water quality variability. Accordingly, the goal of this research was to create a water quality sensor platform including data acquisition, storage, and mining methods able to monitor, and ultimately improve, water quality within buildings. The platform was used to monitor water temperature, pH, conductivity, oxidation–reduction potential, dissolved oxygen, and chlorine using sensors only. Other building data infrastructure, specifically Wi‐Fi logins by occupants, were used to approximate activity rates and associated water use. An advanced machine‐learning technique, gradient boosting machines, predicted the chlorine residuals throughout the building plumbing network better than multivariate linear regression models. Finally, the implications of water quality monitoring on costs, scalability, reliability, human dimensions, regulatory compliance, and future green building designs are considered. 
    more » « less
  5. Herrera, Manuel (Ed.)
    Three buildings that were repurposed for use as an elementary school were shutdown for three months in response to the pandemic. Building cold and hot water quality was monitored before reopening to detect and resolve chemical and microbiological problems. The authors collected first draw pre-flush and post-flush water samples. First draw water samples did not contain detectable disinfectant residual, but nickel and lead sometimes exceeded the health-based action limits for cold water (max. 144 μg Ni/L, 3.4 μg Pb/L). Stagnant cold water at a bathroom sink (188 MPN/100 mL) and drinking water fountain (141.6 MPN/100 mL), in the same building, exceeded the L . pneumophila thresholds advised by the World Health Organization (WHO) (10 CFU/mL) and American Industrial Hygiene Association (AIHA) (100 CFU/mL). Fixture flushing was conducted to remove cold and hot stagnant water and no L . pneumophila was detected immediately after flushing. Two weeks after no subsequent building water use, chemical and microbiological contaminant levels were found to be similar to levels prior to flushing with one exception. The maximum L . pneumophila level (kitchen sink, hot water: 61.1 MPN/100 mL) was found in a different building than the prior maximum detections. No repeat positive locations for L . pneumophila were found during the second visit, but new fixtures were positive the organism. When this study was conducted no evidence-based guidelines for plumbing recommissioning were available. A single plumbing flush reduced heavy metal and L . pneumophila levels below WHO and AIHA thresholds in all three buildings. Additional work is needed to examine the role of building size, type and plumbing design on fixture water quality in shutdown buildings. 
    more » « less