Good indoor air quality in office environments is essential for occupant health and productivity. In open-plan offices, displacement ventilation has been recognized for its higher efficiency compared to mixing ventilation. This study evaluates the performance of displacement ventilation in an open-plan office under cooling and heating conditions, considering various supply ventilation rates, supply air temperatures, and occupancy levels. Field measurements were conducted over three months in a living laboratory office in a high-performance building. The indoor environment was controlled by an independent variable air volume (VAV) air conditioning system. The supply ventilation rate ranged from 6 to 12 h^−1. Real-time measurements of carbon dioxide (CO2) concentrations in the supply air, return air, and breathing zone of the office were conducted to assess occupants’ exposure to CO2 and ventilation efficiency. The results show that the supply ventilation rate plays an important role in shaping the air distribution and overall effectiveness of the mechanical ventilation system. Higher supply ventilation rates can enhance air distribution robustness, improving ventilation efficiency and reducing CO2 exposure under both cooling and heating conditions. These findings also suggest the need for an optimized control logic that differs from the conventional control logic used in VAV systems. Specifically, during the heating condition of displacement ventilation, it is recommended to maintain the supply ventilation rate at a higher level to effectively mitigate the impact of occupant behavior on air quality, minimize CO2 exposure risks, and ensure a more robust and reliable indoor air distribution. 
                        more » 
                        « less   
                    This content will become publicly available on April 1, 2026
                            
                            Spatiotemporal Variations in Ozone and Carbon Dioxide Concentrations in an HVAC System of a LEED-Certified Office Building
                        
                    
    
            Indoor air quality (IAQ) is crucial for the health, well-being, and productivity of office occupants. IAQ is strongly influenced by occupancy and the operational mode of the heating, ventilation, and air conditioning (HVAC) system. This study investigates the spatiotemporal variations in ozone (O3) and carbon dioxide (CO2) concentrations throughout the HVAC system of a LEED-certified office building. A four-month field measurement campaign was conducted at the Ray W. Herrick Laboratories, employing an automated multi-point sampling system to monitor O3 and CO2 at eight locations throughout the HVAC system. The objectives of this study are to characterize the spatiotemporal distribution of these gases under different ventilation modes and occupancy levels, and to identify O3 loss mechanisms in the office and its HVAC system. Spatiotemporal variations in O3 and CO2 concentrations were observed throughout the HVAC system. Results indicate that outdoor air exchange rates (AERs) significantly impact indoor O3 levels, with higher AERs resulting in increased indoor O3 but reduced CO2 concentrations. Measurements reveal that HVAC filters and ducts contribute to O3 loss, with up to 18% O3 removal observed in the longest HVAC duct segment. Additionally, occupancy influences O3 deposition onto human skin and clothing surfaces. This research underscores the limitations of ventilation standards that focus only on CO2, highlighting the need for ventilation strategies that consider the effects of occupancy and outdoor AERs on different gases. By integrating multi-point gas sampling into building automation systems, more effective control strategies can be developed to enhance IAQ and occupant health while reducing energy consumption. 
        more » 
        « less   
        
    
                            - Award ID(s):
- 1847493
- PAR ID:
- 10632933
- Publisher / Repository:
- Elsevier
- Date Published:
- Journal Name:
- Building and Environment
- Volume:
- 274
- Issue:
- C
- ISSN:
- 0360-1323
- Page Range / eLocation ID:
- 112651
- Format(s):
- Medium: X
- Sponsoring Org:
- National Science Foundation
More Like this
- 
            
- 
            Science for Society Buildings account for a significant fraction of the land area in cities and actively exchange air with their proximate outdoor environments via mechanical ventilation systems. However, the direct impact of buildings on urban air pollution remains poorly characterized. Due to reductions in traffic-associated emissions of volatile organic compounds (VOCs), volatile chemical products, which are widely used inside buildings, have become a major VOC source in urban areas. Indoor-generated VOCs are likely to be an important contributor to the VOC burden of the urban atmosphere, and ventilation systems provide a pathway for VOCs to be released outdoors. Here, we show how modern buildings act as significant emission sources of VOCs for the outdoor environment. Our results demonstrate that future air quality monitoring efforts in cities need to account for direct VOC discharge from buildings in order to capture emerging sources of environmental pollution that can impact the climate and human health. Summary Urban air undergoes transformations as it is actively circulated throughout buildings via ventilation systems. However, the influence of air exchange between outdoor and indoor atmospheres on urban air pollution is not well understood. Here, we quantify how buildings behave as a dynamic source and sink for urban air pollutants via high-resolution online mass spectrometry measurements. During our field campaign in a high-performance office building, we observed that the building continually released volatile organic compounds (VOCs) into the urban air and removed outdoor ozone and fine particulate matter. VOC emissions from people, their activities, and surface reservoirs result in significant VOC discharge from the building to the outdoors. Per unit area, building emissions of VOCs are comparable to traffic, industrial, and biogenic emissions. The building source-sink behavior changed dynamically with occupancy and ventilation conditions. Our results demonstrate that buildings can directly influence urban air quality due to substantial outdoor-indoor air exchange.more » « less
- 
            Natural ventilation is used to cool buildings and cut energy costs by inducing airflow through building openings without the use of mechanical ventilation and cooling systems. However, prior research has documented increased introduction of particles into indoor environments that are naturally ventilated, with associated health consequences. The recently updated ASHRAE Standard 62.1–2019: Ventilation for Acceptable Indoor Air Quality Natural Ventilation Procedure (NVP) prescribes opening sizes as a function of occupant density and geometry for use as a ventilation strategy, a change from the previous standard. The current work quantifies the indoor air quality impacts of implementing the Standard 62.1–2019 Natural Ventilation Procedure in the United States and compares it to the 62.1-specified ventilation rate procedure. This is done via coupled transient simulation of CONTAM 3.4 and EnergyPlus 9.1. Three pollutant classes were identified to represent a broad range of contaminants: outdoor-generated pollutants, pollutants generated indoors by humans, and pollutants generated indoors by the building itself. With boundary conditions from measured weather and outdoor pollutant data for 13 representative locations throughout the U.S., our modeling first found 41%–185% annual average increase in ventilation rates over its mechanical counterpart if the NVP is used across the geometries and occupant densities in the Standard. Due to elevated ventilation rates, the Natural Ventilation Procedure reduced building-generated and occupant-generated contaminant concentrations during occupied hours by an average of 17%–61% compared to the ventilation rate procedure. Outdoor-generated fine particles averaged 2.1–2.5 times the concentrations indoors when using the NVP as compared to mechanical ventilation with a MERV-8 filter and 7.8–10.4 times the concentration of a mechanical system with a MERV-13 filter. Both ventilation rates and concentrations were substantially climate-specific and somewhat window geometry-specific. We further showed that increased filtration is needed in many cases to keep up with increased effective NVP rates in the 2019 Standard if acceptable levels of indoor particles are to be achieved, and we offer suggestions for improving the Standard.more » « less
- 
            People spend approximately 90% of their time indoors, making effective indoor air quality (IAQ) monitoring crucial for occupants’ well-being. Traditional IAQ monitoring primarily focuses on carbon dioxide ( ) levels to inform the operation of Heating, Ventilation, and Air Conditioning (HVAC) systems. However, HVAC systems often overlook other critical IAQ metrics, such as volatile organic compounds (VOC), which may correspond better to occupant activities in some cases. This naturalistic study, conducted over four months at the University of Virginia, addresses this significant gap by observing changes in VOC and levels across various times, events, and spaces, including conference rooms, single occupancy offices, and common open-space areas. We aimed to determine whether can be the only representative of IAQ for dynamically adjusting the ventilation rates within this testbed. A key focus was on poor IAQ instances where levels were below the recommended levels, but VOC concentrations exceeded them, potentially impacting occupants’ health and well-being. Our results revealed that in the studied conference room, poor IAQ conditions prevailed 71% of the time during occupancy, in contrast to lower rates in single occupancy offices (11%, 7%, and 16%). Notably, while social events influenced levels less, VOC levels significantly increased in all open-space areas. These findings challenge the conventional reliance on monitoring for IAQ management, highlighting the necessity of incorporating comprehensive IAQ metrics in HVAC systems. The study underscores the critical need for dynamic HVAC systems that adapt to real-time IAQ conditions, a vital step towards enhancing indoor environmental quality in various settings.more » « less
- 
            While ventilation is crucial for ensuring indoor air quality and occupant health, introducing fresh air can lead to increased latent loads due to dehumidification, particularly, in humid climates. The Dedicated Outdoor Air System (DOAS) has gained attention for its ability to supply all fresh air while decoupling latent and sensible loads in buildings. Integrating a desiccant wheel (DW) into the DOAS further enhances its dehumidification performance compared to conventional cooling-based methods. This study proposes a modeling approach leveraging the Julia language and its equation-based acausal modeling framework to analyze the energy performance of DOAS systems, highlighting Julia’s potential in heating, ventilation, and air-conditioning (HVAC) applications. Specifically, we modeled two configurations of DW-based DOAS: one using an active DW and the other using a passive DW. The main modeling components include a desiccant wheel, a thermal network-based office room model considering sensible and latent loads, coils and local controllers. A simulation case study was then conducted to compare the energy performance of the two DOAS configurations over one week during the cooling season in Houston, TX. This study presents a preliminary workflow for HVAC modeling and optimization using a Julia-based symbolic modeling framework, highlighting its potential over conventional methods. The framework is extendable for a further high-fidelity modeling and advanced control analysis of DOAS, and other HVAC equipment and systems.more » « less
 An official website of the United States government
An official website of the United States government 
				
			 
					 
					