Title: Investigating the Vulnerabilities of the Direct Transfer Trip Scheme for Network Protector Units in the Secondary Networks of Electric Power Distribution Grids
Network protector units (NPUs) are crucial parts of the protection of secondary networks to effectively isolate faults occurring on the primary feeders. When a fault occurs on the primary feeder, there is a path of the fault current going through the service transformers that causes a negative flow of current on the NPU connected to the faulted feeder. Conventionally, NPUs rely on the direction of current with respect to the voltage to detect faults and make a correct trip decision. However, the conventional NPU logic does not allow the reverse power flow caused by distributed energy resources installed on secondary networks. The communication-assisted direct transfer trip logic for NPUs can be used to address this challenge. However, the communication-assisted scheme is exposed to some vulnerabilities arising from the disruption or corruption of the communicated data that can endanger the reliable operation of NPUs. This paper evaluates the impact of the malfunction of the communication system on the operation of communication-assisted NPU logic. To this end, the impact of packet modification and denial-of-service cyberattacks on the communication-assisted scheme are evaluated. The evaluation was performed using a hardware-in-the-loop (HIL) co-simulation testbed that includes both real-time power system and communication network digital simulators. This paper evaluates the impact of the cyberattacks for different fault scenarios and provides a list of recommendations to improve the reliability of communication-assisted NPU protection.  more » « less
Award ID(s):
2330582
PAR ID:
10641472
Author(s) / Creator(s):
; ; ; ;
Publisher / Repository:
MDPI Open Access Journal
Date Published:
Journal Name:
Energies
Volume:
18
Issue:
17
ISSN:
1996-1073
Page Range / eLocation ID:
4691
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Due to limited amplitude and controlled phase of current supplied by inverter-interfaced renewable power plants (IIRPPs), the IIRPP-side distance protection of lines connected to IIRPPs fails to detect the fault location accurately, so it may malfunction. The composite sequence network of a line connected to an IIRPP during asymmetrical faults is analyzed, and an adaptive distance protection based on the analytical model of additional impedance is proposed in this study. Based on open circuit property of negative-sequence network at the IIRPP-side, the equivalent impedance of power grid and current flowing through fault point are calculated in real-time using local measurements, which are substituted into the analytical model of additional impedance to calculate fault location. In the case of negative-sequence reactive current injection from IIRPPs during asymmetrical faults, the error of calculating fault point current from local measurements is analyzed and corrected to ensure reliability of the proposed protection. The proposed protection alleviates the effect of fault resistance in a system with weak sources. In addition, the proposed protection can adapt to different grid codes (GCs), the operation mode change of the power grid, and the capacity change of the IIRPP. PSCAD/EMTDC test results verify the effectiveness of the proposed protection. 
    more » « less
  2. Inverter-based resources (IBRs) exhibit distinct short-circuit characteristics that challenge traditional protective relays designed for systems dominated by synchronous generators. While research often focuses on IBRs’ positive-sequence currents during faults, their zero- and negative-sequence responses under unsymmetrical faults remain underexplored. Factors such as transformer configurations and grounding methods further complicate the design of protection schemes relying on these sequence components. This paper enhances the understanding of IBR short-circuit behavior during both symmetrical and unsymmetrical faults and investigates the impact of various transformer configurations on these behaviors. We highlight the limitations of traditional protective relays in safeguarding IBRs due to their constrained fault current levels, minimal negative-sequence components, and, in many cases, the absence of zero-sequence currents. To address these challenges, a novel incremental focused directional protection scheme is introduced. This approach offers enhanced fault detection capabilities under the complex conditions posed by high renewable energy penetration and diverse transformer configurations. The proposed method provides a robust solution for ensuring reliable protection in modern power systems with high integration of IBRs, contributing to improved grid stability and resilience. 
    more » « less
  3. The fast-growing installation of solar PVs has a significant impact on the operation of distribution systems. Grid-tied solar inverters provide reactive power capability to support the voltage profile in a distribution system. In comparison with traditional inverters, smart inverters have the capability of real time remote control through digital communication interfaces. However, cyberattack has become a major threat with the deployment of Information and Communications Technology (ICT) in a smart grid. The past cyberattack incidents have demonstrated how attackers can sabotage a power grid through digital communication systems. In the worst case, numerous electricity consumers can experience a major and extended power outage. Unfortunately, tracking techniques are not efficient for today’s advanced communication networks. Therefore, a reliable cyber protection system is a necessary defense tool for the power grid. In this paper, a signature-based Intrusion Detection System (IDS) is developed to detect cyber intrusions of a distribution system with a high level penetration of solar energy. To identify cyberattack events, an attack table is constructed based on the Temporal Failure Propagation Graph (TFPG) technique. It includes the information of potential cyberattack patterns in terms of attack types and time sequence of anomaly events. Once the detected anomaly events are matched with any of the predefined attack patterns, it is judged to be a cyberattack. Since the attack patterns are distinguishable from other system failures, it reduces the false positive rate. To study the impact of cyberattacks on solar devices and validate the performance of the proposed IDS, a realistic Cyber-Physical System (CPS) simulation environment available at Virginia Tech (VT) is used to develop an interconnection between the cyber and power system models. The CPS model demonstrates how communication system anomalies can impact the physical system. The results of two example cyberattack test cases are obtained with the IEEE 13 node test feeder system and the power system simulator, DIgSILENT PowerFactory. 
    more » « less
  4. This article identifies and validates the use of ultrafast silicon carbide (SiC) junction field effect transistor (JFET)-based self-powered solid-state circuit breakers (SSCBs) as the enabling protective device for a 340 Vdc residential dc community microgrid. These SSCBs will be incorporated into a radial distribution system in order to enhance fault discrimination through autonomous operation. Because of the nature and characteristics of short-circuit fault inception in dc microgrids, the time-current trip characteristics of protective devices must be several orders of magnitude faster than conventional circuit breakers. The proposed SSCBs detect short-circuit faults by sensing the sudden voltage rise between its two power terminals and draw power from the fault condition itself to turn off SiC JFETs and then, coordinate with no-load contacts that can isolate the fault. Depending upon the location of the SSCBs in the microgrid, either unidirectional or bidirectional implementations are incorporated. Cascaded SSCBs are tuned using a simple resistor change to enable fault discrimination between upstream high-current feeds and downstream lower current branches. Operation of one of the SSCBs and three in cascaded arrangements are validated both in simulation and with a hardware test platform. Thermal impact on the SSCB is discussed as well. The target application is a residential dc microgrid that will be installed as part of a revitalization effort of an inner city Milwaukee neighborhood. 
    more » « less
  5. A decentralized adaptive scheme is proposed for protection coordination of microgrids. In the proposed scheme, a set of agents around the fault location negotiate with each other to reach the best protection coordination strategy upon the occurrence of a fault. Adopting a protective layer, agents are arranged in a number of groups where the members in each group can interact with each other. Considering the operational uncertainties of the respective circuit breakers and communication links, the best fault clearance strategy is determined by analyzing the probability of correct operation of all proposed strategies and considering the least number of probable outages. This is done by calculating the fault currents flowing through the respective circuit breakers and the Latency of the communication links. The efficiency of the proposed scheme is demonstrated by comparing the simulation results of a sample network with those obtained using the conventional central adaptive protection approach. 
    more » « less