Title: CFD Modeling of the Distribution of Airborne Particulate Contaminants Inside Data Center Hardware
Abstract

Modern-day data center administrators are finding it increasingly difficult to lower the costs incurred in mechanical cooling of their IT equipment. This is especially true for high-performance computing facilities like Artificial Intelligence, Bitcoin Mining, and Deep Learning, etc. Airside Economization or free air cooling has been out there as a technology for a long time now to reduce the mechanical cooling costs. In free air cooling, under favorable ambient conditions of temperature and humidity, outside air can be used for cooling the IT equipment. In doing so, the IT equipment is exposed to sub-micron particulate/gaseous contaminants that might enter the data center facility with the cooling airflow.

The present investigation uses a computational approach to model the airflow paths of particulate contaminants entering inside the IT equipment using a commercially available CFD code. A Discrete Phase Particle modeling approach is chosen to calculate trajectories of the dispersed contaminants. Standard RANS approach is used to model the airflow in the airflow and the particles are superimposed on the flow field by the CFD solver using Lagrangian particle tracking. The server geometry was modeled in 2-D with a combination of rectangular and cylindrical obstructions. This was done to comprehend the effect of change in the obstruction type and aspect ratio on particle distribution. Identifying such discrete areas of contaminant proliferation based on concentration fields due to changing geometries will help with the mitigation of particulate contamination related failures in data centers.

 
more » « less
Award ID(s):
1738811
NSF-PAR ID:
10276624
Author(s) / Creator(s):
; ; ; ; ;
Date Published:
Journal Name:
ASME 2020 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Abstract Continuous rise in cloud computing and other web-based services propelled the data center proliferation seen over the past decade. Traditional data centers use vapor-compression-based cooling units that not only reduce energy efficiency but also increase operational and initial investment costs due to involved redundancies. Free air cooling and airside economization can substantially reduce the information technology equipment (ITE) cooling power consumption, which accounts for approximately 40% of energy consumption for a typical air-cooled data center. However, this cooling approach entails an inherent risk of exposing the ITE to harmful ultrafine particulate contaminants, thus, potentially reducing the equipment and component reliability. The present investigation attempts to quantify the effects of particulate contamination inside the data center equipment and ITE room using computational fluid dynamics (CFD). An analysis of the boundary conditions to be used was done by detailed modeling of ITE and the data center white space. Both two-dimensional and three-dimensional simulations were done for detailed analysis of particle transport within the server enclosure. An analysis of the effect of the primary pressure loss obstructions like heat sinks and dual inline memory modules inside the server was done to visualize the localized particle concentrations within the server. A room-level simulation was then conducted to identify the most vulnerable locations of particle concentration within the data center space. The results show that parameters such as higher velocities, heat sink cutouts, and higher aspect ratio features within the server tend to increase the particle concentration inside the servers. 
    more » « less
  2. Most of the thermal management technologies concentrate on managing airflow to achieve the desired server inlet temperature (supply air operating set point) and not to manage/improve the amount of cool air (CFM) that each computer rack (i.e. IT servers) should receive in order to remove the produced heat. However, airflow is equally important for quantifying adequate cooling to IT equipment, but it is more challenging to obtain a uniform airflow distribution at the inlet of computer racks. Therefore, as a potential option for improving airflow distribution is to eliminate the sources of non-uniformities such as maldistribution of under-floor plenum pressure field caused by vortices. Numerous researchers focus on the adverse effects of under-floor blockages. This study focused to numerically investigate the positive impact of selectively placed obstructions (on-purpose air-directors); referred as partitions; Quantitative and qualitative analysis of underfloor plenum pressure field, perforated tiles airflow rate and racks inlet temperature with and without partitions using two Computational Fluid Dynamics (CFD) models, which were built using Future Facilities 6SigmaRoom CFD tool. First, a simple data center model was used to quantify the partitions benefits for two different systems; Hot Aisle Containment (HAC) compared to an open configuration. Second, the investigation was expanded using a physics-based experimentally validated CFD model of medium size data center (more complicated data center geometry) to compare different types of proposed partitions. Both models results showed that partition type I (partitions height of $\frac{2}{3}$ of plenum depth measured from the subfloor) eliminates the presence of vortices in the under-floor plenum and hence, more uniform pressure differential across the perforated tiles that drives more uniform airflow rates. In addition, the influence of proposed partitions on the rack inlet temperature was reported through a comparison between open versus hot aisle containment. The results showed that the partitions have a minor effect on the rack inlet temperature for the hot aisle containment system. However, the partitions significantly improve the tiles flowrate. On the other hand, for the open system, the presence of partitions has improved the tiles airflow rate, rack inlet temperature and hence eliminate the hot spots formation at computer rack inlet 
    more » « less
  3. Abstract Airside economizers lower the operating cost of data centers by reducing or eliminating mechanical cooling. It, however, increases the risk of reliability degradation of information technology (IT) equipment due to contaminants. IT Equipment manufacturers have tested equipment performance and guarantee the reliability of their equipment in environments within ISA 71.04-2013 severity level G1 and the ASHRAE recommended temperature-relative humidity (RH) envelope. IT Equipment manufacturers require data center operators to meet all the specified conditions consistently before fulfilling warranty on equipment failure. To determine the reliability of electronic hardware in higher severity conditions, field data obtained from real data centers are required. In this study, a corrosion classification coupon experiment as per ISA 71.04-2013 was performed to determine the severity level of a research data center (RDC) located in an industrial area of hot and humid Dallas. The temperature-RH excursions were analyzed based on time series and weather data bin analysis using trend data for the duration of operation. After some period, a failure was recorded on two power distribution units (PDUs) located in the hot aisle. The damaged hardware and other hardware were evaluated, and cumulative corrosion damage study was carried out. The hypothetical estimation of the end of life of components is provided to determine free air-cooling hours for the site. There was no failure of even a single server operated with fresh air-cooling shows that using evaporative/free air cooling is not detrimental to IT equipment reliability. This study, however, must be repeated in other geographical locations to determine if the contamination effect is location dependent. 
    more » « less
  4. Abstract An increasingly common power saving practice in data center thermal management is to swap out air cooling unit blower fans with electronically commutated plug fans, Although, both are centrifugal blowers. The blade design changes: forward versus backward curved with peak static efficiencies of 60% and 75%, respectively, which results in operation power savings. The side effects of which are not fully understood. Therefore, it has become necessary to develop an overall understanding of backward curved blowers and compare the resulting flow, pressure, and temperature fields with forwarding curved ones in which the induced fields are characterized, compared, and visualized in a reference data center which may aid data center planning and operation when making the decisions of which computer room air handler (CRAH) technology to be used. In this study, experimental and numerical characterization of backward curved blowers is introduced. Then, a physics-based computational fluid dynamics model is built using the 6sigmaroom tool to predict/simulate the measured fields. Five different scenarios were applied at the room level for the experimental characterization of the cooling units and another two scenarios were applied for comparison and illustration of the interaction between different CRAH technologies. Four scenarios were used to characterize a CRAH with backward curved blowers, during which a CRAH with forwarding curved was powered off. An alternate arrangement was examined to quantify the effect of possible flow constraints on the backward curved blower's performance. Then parametric and sensitivity of the baseline modeling are investigated and considered. Different operating conditions are applied at the room level for experimental characterization, comparison, and illustration of the interaction between different CRAH technologies. The measured data is plotted and compared with the computational fluid dynamics (CFD) model assessment to visualize the fields of interest. The results show that the fields are highly dependent on CRAH technology. The tile to CRAH airflow ratios for the flow constraints of scenarios 1, 2, 3, and 4 are 85.5%, 83.9%, 61%, and 59%, respectively. The corresponding leakage ratios are 14.5%, 16%, 38.9%, and 41%, respectively. Furthermore, the validated CFD model was used to investigate and compare the airflow pattern and plenum pressure distribution. Lastly, it is notable that a potential side effect of backward curved technology is the creation of an airflow dead zone. 
    more » « less
  5. Over the past few years, there has been an ever increasing rise in energy consumption by IT equipment in Data Centers. Thus, the need to minimize the environmental impact of Data Centers by optimizing energy consumption and material use is increasing. In 2011, the Open Compute Project was started which was aimed at sharing specifications and best practices with the community for highly energy efficient and economical data centers. The first Open Compute Server was the ‘ Freedom’ Server. It was a vanity free design and was completely custom designed using minimum number of components and was deployed in a data center in Prineville, Oregon. Within the first few months of operation, considerable amount of energy and cost savings were observed. Since then, progressive generations of Open Compute servers have been introduced. Initially, the servers used for compute purposes mainly had a 2 socket architecture. In 2015, the Yosemite Open Compute Server was introduced which was suited for higher compute capacity. Yosemite has a system on a chip architecture having four CPUs per sled providing a significant improvement in performance per watt over the previous generations. This study mainly focuses on air flow optimization in Yosemite platform to improve its overall cooling performance. Commercially available CFD tools have made it possible to do the thermal modeling of these servers and predict their efficiency. A detailed server model is generated using a CFD tool and its optimization has been done to improve the air flow characteristics in the server. Thermal model of the improved design is compared to the existing design to show the impact of air flow optimization on flow rates and flow speeds which in turn affects CPU die temperatures and cooling power consumption and thus, impacting the overall cooling performance of the Yosemite platform. Emphasis is given on effective utilization of fans in the server as compared to the original design and improving air flow characteristics inside the server via improved ducting. 
    more » « less