Title: An Experimental Investigation of the Relationship Between Evaporator and Condenser Sizes With Oscillating Heat Pipe Start-Up
Abstract Oscillating Heat Pipes (OHPs) are unique two-phase heat transfer devices with many advantages over standard and more widely adopted thermal control devices. Specifically, OHPs are able to operate passively, over a wide temperature range, and under high heat fluxes, with few design constraints. OHPs operate based on the process of evaporating and condensing a working fluid on opposite ends of a series of serpentine channels. The pressure difference causes an oscillating behavior of the fluid to travel along the direction of the channels enabling a high heat transfer rate. The capability of this technology has garnered much attention and interest for a variety of applications in different fields. While as a thermal management device, OHP technology shows much promise, there is still much to be understood about the fundamental principles of its operation. One of the most important aspects of OHP operation that is still not well understood is the phenomena known as “start-up”. Start-up is when the proper conditions of an OHP are created such that the operating, oscillatory process of an OHP is enabled to begin. In this work, experimental testing is performed to investigate the relationship between evaporator and condenser length on OHP start-up. In this study, combinations of small, medium, and large length evaporators and condensers were used on a 42-turn OHP with 1 mm square channels, charged with R134a to 50% fill ratio with the goal to quantify the minimum heat that would initiate start-up. Before this test could be performed, issues in consistency of the start-up of OHP had to be resolved. A method to “reset” the liquid-vapor distribution to overcome any adverse history from previous OHP operation developed is discussed. Then, a zero-heat input method of confirming a liquid-vapor distribution favorable to start-up is outlined. After developing this method to achieve a consistent start-up heat input in the OHP, tests were performed for nine different configurations of large, medium, and small evaporator and condensers, to determine their relationship with the minimum heat required to start-up an OHP. It was observed that both the size of the evaporator and condenser both influence the start-up heat load. That is, a large condenser and evaporator can reduce the heat load required to start-up. Additionally, the size of a condenser is much more influential than the size of the evaporator. The overarching discovery is that the process of start-up relies heavily on the history of the OHP i.e., the initial liquid-vapor distribution of the working fluid in the channels. In measuring start-up, it is important to recognize and address how the current state of the OHP can lead to inconsistent results.  more » « less
Award ID(s):
2112554
PAR ID:
10529196
Author(s) / Creator(s):
; ; ; ; ; ; ; ;
Publisher / Repository:
American Society of Mechanical Engineers
Date Published:
ISBN:
978-0-7918-8767-7
Format(s):
Medium: X
Location:
New Orleans, Louisiana, USA
Sponsoring Org:
National Science Foundation
More Like this
  1. A radiative vapor condenser sheds heat in the form of infrared radiation and cools itself to below the ambient air temperature to produce liquid water from vapor. This effect has been known for centuries, and is exploited by some insects to survive in dry deserts. Humans have also been using radiative condensation for dew collection. However, all existing radiative vapor condensers must operate during the nighttime. Here, we develop daytime radiative condensers that continue to operate 24 h a day. These daytime radiative condensers can produce water from vapor under direct sunlight, without active consumption of energy. Combined with traditional passive cooling via convection and conduction, radiative cooling can substantially increase the performance of passive vapor condensation, which can be used for passive water extraction and purification technologies. 
    more » « less
  2. Abstract As small spacecraft technologies develop, thermal management devices need to meet the growing demands of high-powered electronics. Currently being developed to meet this demand in CubeSats is the Additively Manufactured Deployable Radiator Oscillating Heat Pipes (AMDROHP). AMDROHP seeks to implement the high thermal conductivity and two-phase technology of Oscillating Heat Pipes into a unique deployable radiator design for a 3U CubeSat, taking advantage of additive manufacturing capabilities. While much consideration has been put into designing the AMDROHP on its own as a heat exchanger, there is also the need for it to be evaluated thermally at a system-level with the rest of the CubeSat while in orbit. In this study, thermal orbital spacecraft simulations, through the Thermal Desktop software, were performed to analyze how AMDROHP thermally integrates and interacts with the rest of the CubeSat and evaluate the survivability of temperature-sensitive components on the spacecraft. The simulations in this study included an 11th-orbit beta angle sweep for a tumbling orientation of the spacecraft in Low Earth Orbit (LEO). These simulations were performed with two AMDROHP devices in the CubeSat bus, each under a direct 25W heat input and performing with a thermal conductance of 6 W/K, which corresponds to the projected performance of the AMDROHP device while in operation. In this paper, the Thermal Desktop model of the AMDROHP CubeSat includes all major physical components, connections, heat loads, and thermal and optical materials. Then, steps are taken to improve the computational speed of the model. Furthermore, the means of addressing the modeling of the complex two-phase behavior of the OHP is outlined. Then, a number of test cases considering various operating conditions were simulated. From these simulations, orbital temperatures of sensitive components, primarily electronics, were collected and analyzed to find the minimum and maximum operating temperatures across all potential orbits. These temperatures were then evaluated to determine the component’s survivability in a worst-case scenario in orbit. From the results, it was found that, with the projected conductance of AMDROHP, all components operate under safe temperature conditions for any beta angle while in Low Earth Orbit. The evaporator is consistently the hottest component of the spacecraft and electronics boards all maintain survivable temperatures and are not at risk of over or underheating, even at worst case temperatures for all orbits tested. Based on the results and analysis of this conceptual study, it is suggested that AMDROHP will perform as an effective management device for small satellites. 
    more » « less
  3. Abstract This study aims to improve the combined energy efficiency of data center cooling systems and heating/cooling systems in surrounding premises by implementing a modular cooling approach on a 42 U IT rack. The cooling solution uses a close-coupled technique where the servers are air-cooled, and the air in turn is cooled within the rack enclosure using an air-to-refrigerant heat exchanger. The refrigerant passively circulates in a loop as a thermosyphon, making the system self-sustaining during startup and shutdown, self-regulating under varying heat loads, and virtually maintenance-free by eliminating mechanical parts (other than the cabinet fans). A heat load range of 2 kW–7.5 kW is tested on a prototype system. Experimental results reveal stable thermosyphon operation using R1233zd(E) as the working fluid, a maximum evaporator pressure drop of 21.5 kPa at the highest heat load and a minimum thermosyphon resistance of 6.8 mK/W at a heat load of 5.7 kW. The air temperature profile across the load banks (server simulators) and evaporator follow the same profiles with varying heat loads. Heat losses from the cabinet due to natural convection and radiation are of the order of several Watts for heat loads below 4 kW and rise sharply to 1 kW at the highest heat load tested. The system time constant is determined to be 25 min. The heat recovery process can be financially and environmentally beneficial depending on the downstream application. 
    more » « less
  4. Abstract This paper is focused on the modeling of a brazed plate heat exchanger (BPHE) for a novel in-rack cooling loop coupled with heat recovery capability for enhanced thermal management of datacenters. In the proposed technology, the BPHE is acting as a condenser, and the model presented in this study can be applied in either the cooling loop or vapor recompression loop. Thus, the primary fluid enters as either superheated (in the vapor recompression loop) or saturated vapor (in the cooling loop), while the secondary fluid enters as a sub-cooled liquid. The model augments an existing technique from the open literature and is applied to condensation of a low-pressure refrigerant R245fa. The model assumes a two-fluid heat exchanger with R245fa and water as the primary and secondary fluids, respectively, flowing in counterflow configuration; however, the model can also handle parallel flow configuration. The 2-D model divides the heat exchanger geometry into a discrete number of slices to analyze heat transfer and pressure drops (including static, momentum and frictional losses) of both fluids, which are used to predict the exit temperature and pressure of both fluids. The model predicts the exchanger duty based on the local energy balance. The predicted values of fluid output properties (secondary fluid temperature and pressure, and primary fluid vapor quality and pressure) along with heat exchanger duty show good agreement when compared against a commercial software. 
    more » « less
  5. null (Ed.)
    This paper is focused on the modeling of a brazed plate heat exchanger (BPHE) for a novel in-rack cooling loop coupled with heat recovery capability for enhanced thermal management of datacenters. In the proposed technology, the BPHE is acting as a condenser, and the model presented in this study can be applied in either the cooling loop or vapor recompression loop. Thus, the primary fluid enters as either superheated (in the vapor recompression loop) or saturated vapor (in the cooling loop), while the secondary fluid enters as a sub-cooled liquid. The model augments an existing technique from the open literature and is applied to condensation of a low-pressure refrigerant R245fa. The model assumes a two-fluid heat exchanger with R245fa and water as the primary and secondary fluids, respectively, flowing in counterflow configuration; however, the model can also handle parallel flow configuration. The 2-D model divides the heat exchanger geometry into a discrete number of slices to analyze heat transfer and pressure drops (including static, momentum and frictional losses) of both fluids, which are used to predict the exit temperature and pressure of both fluids. The model predicts the exchanger duty based on the local energy balance. The predicted values of fluid output properties (secondary fluid temperature and pressure, and primary fluid vapor quality and pressure) along with heat exchanger duty show good agreement when compared against a commercial software. 
    more » « less