Title: Tri-Level Linear Programming Model for Automatic Load Shedding Using Spectral Clustering
Traditional load shedding schemes can be inadequate in grids with high renewable penetration, leading to unstable events and unnecessary grid islanding. Although for both manual and automatic operating modes load shedding areas have been predefined by grid operators, they have remained fixed, and may be sub-optimal due to dynamic operating conditions. In this work, a distributed tri-level linear programming model for automatic load shedding to avoid system islanding is presented. Preventing islanding is preferred because it reduces the need for additional load shedding besides the disconnection of transmission lines between islands. This is crucial as maintaining the local generation-demand balance is necessary to preserve frequency stability. Furthermore, uneven distribution of generation resources among islands can lead to increased load shedding, causing economic and reliability challenges. This issue is further compounded in modern power systems heavily dependent on non-dispatchable resources like wind and solar. The upper-level model uses complex power flow measurements to determine the system areas to shed load depending on actual operating conditions using a spectral clustering approach. The mid-level model estimates the area system state, while the lower-level model determines the locations and load values to be shed. The solution is practical and promising for real-world applications.  more » « less
Award ID(s):
2122313
PAR ID:
10529258
Author(s) / Creator(s):
; ; ;
Publisher / Repository:
IEEE
Date Published:
ISBN:
979-8-3503-1360-4
Page Range / eLocation ID:
1 to 5
Subject(s) / Keyword(s):
Automatic load shedding intentional control islanding spectral clustering
Format(s):
Medium: X
Location:
Washington, DC, USA
Sponsoring Org:
National Science Foundation
More Like this
  1. Reliability of the power grid can be improved by the use of microgrids (MGs) concept, which regulates the voltage and frequency at the point of common coupling (PCC) during normal and/or faulty conditions. Droop characteristics based hierarchical control strategies are commonly used in MGs, where power converters can operate in parallel. However, the need of multiple control loops not only adds complexity to the controller design, but also reduces the dynamic response of the system. In the future power system, grid-tied converters with fast dynamic response are desired to handle the uncertainties induced by high penetration of distributed energy resources. Therefore, this paper presents a novel model predictive control to ensure fast dynamic response of high power three-level converters in stand-alone operating mode as well as grid-tied operating mode. The proposed controller is applied to a MG which consists of a solar inverter connected in parallel with an energy storage system to the PCC, where a local load is tied. Both simulation and experimental results are presented to demonstrate robustness and the high dynamic performance of the proposed controller under rapidly changing atmospheric conditions and different grid operating modes. 
    more » « less
  2. One of the main desired capabilities of the smart grid is ‘self‐healing’, which is the ability to quickly restore power after a disturbance. Due to critical outage events, customer demand or load is at times disconnected or shed temporarily. While deterministic optimisation models have been devised to help operators expedite load shed recovery by harnessing the flexibility of the grid's topology (i.e. transmission line switching), an important issue that remains unaddressed is how to cope with the uncertainty in generation and demand encountered during the recovery process. This study introduces two‐stage stochastic models to deal with these uncertain parameters, and one of them incorporates conditional value‐at‐risk to measure the risk level of unrecovered load shed. The models are implemented using a scenario‐based approach where the objective is to maximise load shed recovery in the bulk transmission network by switching transmission lines and performing other corrective actions (e.g. generator re‐dispatch) after the topology is modified. The benefits of the proposed stochastic models are compared with a deterministic mean‐value model, using the IEEE 118‐ and 14‐bus test cases. Experiments highlight how the proposed approach can serve as an offline contingency analysis tool, and how this method aids self‐healing by recovering more load shedding. 
    more » « less
  3. null (Ed.)
    With the growth in penetration number and power level of renewable energy resources, the need for a compact and high efficient solid state transformer becomes more important. The aim of this paper is to design a compact solid state transformer for microgrid application. The proposed transformer has four ports integrated on a single common core. Thus, it can integrate different renewable energy resources and energy storage systems. The transformer is operating at 50kHz switching frequency, and each port can handle 25kW rated power. In this paper, the ports are chosen to represent a realistic industrial microgrid model consisting of grid, energy storage system, photovoltaic system, and load. The grid port is designed to operate at 4160V AC, while the other three ports operate at 400V. Moreover, the grid, energy storage, and photovoltaic ports are active ports with dual active bridge topologies, while the load port is a passive port with full bridge rectifier one. In this paper, an extensive and complete design and modeling of the entire solid state transformer is presented. The proposed design is first validated with simulation results, and then the proposed transformer is implemented. Some preliminary experimental tests are also performed and the obtained results are reported. 
    more » « less
  4. Abstract Enhancing the resilience and reliability of power grids is crucial amid rising cyber threats and system complexities. To address these challenges, this paper proposes an energy‐efficient, consortium blockchain‐based global alarm system for power grid management. Using smart contracts and the proof of‐authority consensus algorithm, the alarm system triggers global alarms upon detecting local anomalies, ensuring a prompt response to partition the power grid and mitigate failures. The effectiveness is validated by simulating the Iberian power system with 15 providers from various regions. Key metrics, such as load shedding, damage reduction, energy consumption, latency, and transaction costs, are used to assess the performance. Through simulations, we show that the blockchain‐based system effectively limits the damage propagation and the load shedding during cascading failures by delaying the onset of instability and maintaining lower damage levels compared to non‐blockchain scenarios. Our investigations reveal that the proposed global alarm mechanism reduces the damage and load shedding by up to 29% and 87%, respectively, showcasing its potential for preventing widespread outages. 
    more » « less
  5. Wildfires pose a growing risk to public safety in regions like the western United States, and, historically, electric power systems have ignited some of the most destructive wildfires. To reduce wildfire ignition risks, power system operators preemptively de-energize high-risk power lines during extreme wildfire conditions as part of "Public Safety Power Shutoff" (PSPS) events. While capable of substantially reducing acute wildfire risks, PSPS events can also result in significant amounts of load shedding as the partially de-energized system may not be able to supply all customer demands. In this work, we investigate the extent to which infrastructure investments can support system operations during PSPS events by enabling reduced load shedding and wildfire ignition risk. We consider the installation of grid-scale batteries, solar PV, and line hardening or maintenance measures (e.g., undergrounding or increased vegetation management). Optimally selecting the locations, types, and sizes of these infrastructure investments requires considering the line de-energizations associated with PSPS events. Accordingly, this paper proposes a multi-period optimization formulation that locates and sizes infrastructure investments while simultaneously choosing line de-energizations to minimize wildfire ignition risk and load shedding. The proposed formulation is evaluated using two geolocated test cases along with realistic infrastructure investment parameters and actual wildfire risk data from the US Geological Survey. We evaluate the performance of investment choices by simulating de-energization decisions for the entire 2021 wildfire season with optimized infrastructure placements. With investment decisions varying significantly for different test cases, budgets, and operator priorities, the numerical results demonstrate the proposed formulation's value in tailoring investment choices to different settings. 
    more » « less