This work presents a robust visual diagnostic framework for analyzing pool boiling phenomena, aimed at quantifying relative changes in heat flux and providing a foundation for future predictive models with limited temperature data. Instead of directly estimating heat flux from visual features, the proposed approach focuses on identifying relative changes in boiling visual patterns to detect a shift in heat flux and infer visual changes that could help in estimating proximity to the critical heat flux (CHF), which is a key threshold beyond which thermal performance rapidly deteriorates. At the core of this framework is a novel metric, morphological similarity, which captures variations in bubble shape and spatial organization using scale invariant feature transform (SIFT)-based feature matching between image pairs. Experimental validation on two different heated surfaces demonstrates that morphological similarity reliably tracks changes in heat flux and strongly correlates with surface superheat, a key thermal parameter. Requiring only minimal data, this method generalizes across two surfaces and offers a scalable, real-time alternative for thermal diagnostics in electronics cooling systems.more » « lessFree, publicly-accessible full text available December 1, 2027
-
Organic phase change material and high thermal conductivity filler composites are effective in thermal energy storage, but their performance can be highly dependent on the volume fraction of the phase change material/filler. In these composites, energy density (energy storage capacity of the composite) can be enhanced by increasing the phase change material volume fraction; in contrast, power density (rate at which the energy is accessed) can be improved by increasing the filler volume fraction. However, both characteristics cannot be increased simultaneously; therefore, the optimum volume fraction is crucial for maximizing the composite’s thermal performance. In this work, we leverage the analogy of the thermal energy storage in phase change material with electrochemical energy storage in batteries through the Ragone framework to determine the optimum design. Furthermore, this paper proposes relationships for the optimum volume fraction as a function of thermal load, geometry, and cutoff temperature during the melting process. The proposed correlations provide a practical tool for designing and optimizing organic phase change material-filler composites and reduce reliance on computationally intensive numerical or experimental trials.more » « lessFree, publicly-accessible full text available April 9, 2027
-
This work aims to develop a data acquisition methodology for visual data-based deep learning models to predict boiling heat flux. Conventional deep learning models often rely on a fixed architecture and uniform training data sampling across the nucleate boiling regime, which can lead to suboptimal performance because visual patterns are sensitive to changes in heat flux. To address this challenge, we developed an approach that uses the Index of Visual Similarity (IVS) to guide training data sampling (𝛥𝑄). To investigate the problem, we developed an interpolation framework that uses high-speed pool-boiling images and leverages global visual features via a VGG-16-based convolutional neural network to estimate heat flux. This model has been used to test the developed IVS-based methodology. The methodology uses IVS as a visual indicator to assess the degree of change in identifiable physical features with respect to heat flux. Hence, changes in IVS can be used to guide the selection of an optimal data sampling distribution across the heat flux range under consideration. The study further examines how the heat flux sampling used for training influences both model accuracy and computation overhead. A Genetic Algorithm (GA) is developed and employed to optimize the training interval, balancing predictive accuracy against computational cost. The optimization results reveal variations in boiling visual patterns across the explored heat flux range of 50-90 W/cm2 . These findings from the genetic algorithm were used to validate the IVS-guided heat flux sampling. Finally, it was observed that an IVS-guided training reduced training time by 39.1% compared with training at the lowest uniform sampling rate (𝛥𝑄 = 1 W/𝑐𝑚2 ), while maintaining high accuracy, with a mean absolute percentage error of 1.59%. Overall, this work demonstrates that efficient data sampling strategies can significantly reduce computational overhead without compromising accuracy, providing new opportunities for AI-driven thermal diagnostics.more » « lessFree, publicly-accessible full text available April 1, 2027
-
Abstract The rapid growth of digitization and data-driven technologies is driving large-scale deployment of data centers worldwide. As societies become increasingly inference-hungry, the energy consumption of data centers continues to rise at an unprecedented rate, with a significant fraction of this energy being expended on thermal management and cooling infrastructure. Improving cooling efficiency has therefore become a critical challenge for the thermal management community, directly impacting both the sustainability and scalability of future computing systems. In this paper, we demonstrate an energy-efficient cooling solution based on chip-integrated two-phase cooling, which leverages liquid-to-vapor phase-change heat transfer to achieve high heat-flux dissipation at reduced pumping power and thermal resistance. This paper investigates an aggressive cooling architecture utilizing direct-on-die two-phase jet impingement on an NVIDIA Tesla V100 GPU without any thermal enhancement structures. By eliminating thermal interface material (TIM) and impinging the working fluid R1233zd(E), a low-global warming potential (GWP) (<1) refrigerant, directly onto the silicon backside, the primary thermal bottleneck is removed. Experimental results demonstrate a junction-to-coolant thermal resistance of 0.056 °C/W and a theoretical pumping power of only 0.172 W versus the conventional air-cooled cold plate of 0.1709 °C/W and a fan power of 39.9 W. Furthermore, the reliability of the direct-on-die cooling technique was validated through 200 h of continuous, stable operation. This study positions direct jet impingement as a highly efficient, compact, and sustainable solution for next-generation high-performance computing environments.more » « lessFree, publicly-accessible full text available June 1, 2027
-
Two-phase jet impingement cooling is a promising solution for high-heat-flux semiconductor thermal management, as it combines strong convective heat transfer with boiling to remove large heat loads at relatively low flow rates and pressure drops. However, practical deployment is hindered by challenges including inconsistent boiling initiation on smooth surfaces, surface dry-out, vapor-induced flow instabilities, and premature critical heat flux (CHF). Excessive vapor generation within confined geometries can disrupt flow uniformity, causing temperature oscillations and unstable operation. To address these challenges, this work presents a confined, direct-on-silicon two-phase jet impingement cooling approach incorporating a porous-wick-assisted phase separation mechanism. The engineered porous wick enhances nucleate boiling and enables in situ phase separation at the boiling surface. Integrated with a custom three-path manifold, the design routes separated liquid and vapor streams, minimizing vapor accumulation within the confined region and suppressing two-phase instabilities. The porous wick is directly printed onto the silicon substrate using advanced additive manufacturing, eliminating the need for a thermal interface material (TIM) and its associated thermal resistance. Thermal–hydraulic characterization using a low-surface-tension dielectric fluid demonstrates that wick-assisted phase separation reduces thermal resistance by 23–29% compared to configurations without phase separation. Extended testing over more than 200 h of continuous operation confirms stable thermal performance and indicates strong potential for long-term reliability. System-level validation is demonstrated in a 1 U server equipped with an NVIDIA V100 GPU (graphics processing unit) incorporating a direct-on-silicon printed wick.more » « lessFree, publicly-accessible full text available June 1, 2027
-
Abstract This work presents a robust visual diagnostic framework for analyzing pool boiling phenomena, aimed at quantifying relative changes in heat flux and providing a foundation for future predictive models with limited temperature data. Instead of directly estimating heat flux from visual features, the proposed approach focuses on identifying relative changes in boiling visual patterns to detect a shift in heat flux and infer proximity to the critical heat flux (CHF), which is a key threshold beyond which thermal performance rapidly deteriorates. At the core of this framework is a novel metric, morphological similarity, which captures variations in bubble shape and spatial organization using Scale Invariant Feature Transform (SIFT)-based feature matching between image pairs. Experimental validation on two different heated surfaces demonstrates that morphological similarity reliably tracks changes in heat flux and strongly correlates with surface superheat, a key thermal parameter. Requiring only minimal data, this method generalizes across two surfaces and offers a scalable, real-time alternative for thermal diagnostics in electronics cooling systems.more » « less
-
In recent years, electronic packaging has evolved significantly to meet demands for higher performance, lower costs, and smaller designs. This shift has led to heterogeneous packaging, which integrates chips of varying stack heights and results in non-uniform heat flux and temperature distributions. These conditions pose substantial thermal management challenges, as they can create large temperature gradients, which increase thermal stress and potentially compromise chip reliability. This study explores single-phase liquid cooling for multi-chip modules (MCMs) through a comprehensive experimental and machine learning approach. It investigates the impact of chip spacing, height, fluid flow rate, fluid inlet location, and heat flux uniformity on chip temperature and the thermohydraulic performance of a commercial cold plate. Results show that increasing coolant flow from 1 LPM to 2 LPM decreased thermal resistance by 26 %, with heat losses remaining below 5 %. The left inlet configuration improved temperature uniformity compared to the right, though both yielded comparable thermal performance. Adjusting heater spacing impacted temperature distribution based on inlet position, and lowering one heater by 1 mm raised its temperatures by 15 ◦C due to increased thermal resistance from thermal interface material. A transient test demonstrated the cold plate’s quick response to power surges, in which there is only a 1 ◦C spike above steady state. Complementing these findings, an Artificial Neural Network (ANN) model was developed with optimized architecture specifically for the unique challenges of this study. The ANN model was rigorously validated using an independent dataset, achieving highly accurate temperature predictions (R2 = 0.99) within 2.5 % of experimentalmore » « less
-
This study explores the latent thermal energy storage potential of an organic phase change material with porous copper foam and its applicability in electronic cooling under varying heat load conditions. The organic phase change material, n-eicosane, is known for its inherently low thermal conductivity of 0.15 W/mK, rendering it vulnerable during power spikes despite its abundant latent heat energy for phase transition from solid to liquid. Porous copper foams are often integrated into n-eicosane to enhance the composite’s thermal conductivity. However, the volume fraction of the phase change material in the porous foam that optimally improves the thermal performance can be dependent on the boundary condition, the cut-off temperature, and the thickness. A finite difference numerical model was developed and utilized to ascertain the energy consumption for the composite of n-eicosane with two kinds of porous copper foam with varying porosity under different heat rates, cut-off temperatures, and thickness. In addition, the results are compared with a metallic phase change material (gallium), a material chosen with a similar melting point but significantly high thermal conductivity and volumetric latent heat. For validation of the numerical model and to experimentally verify the effect of boundary condition (heat rate), experimental investigation was performed for n-eicosane and high porosity copper foam composite at varying heat rates to observe its melting and solidification behaviors during continuous operation until a cut-off temperature of 70 ◦C is reached. Experiments reveal that heat rate influences the amount of latent energy storage capability until a cutoff temperature is reached. For broad comparison, the numerical model was used to obtain the accessed energy and power density and generate thermal Ragone plots to compare and characterize pure gallium and n-eicosane - porous foam composite with varying volume fractions, cutoff temperature, and thickness under volumetric and gravimetric constraints. Overall, the proposed framework in the form of thermal Ragone plots effectively delineates the optimal points for various combinations of heat rate, cutoff point, and aspect ratio, affirming its utility for comprehensive design guidelines for PCM-based composites for electronic cooling applicationsmore » « less
-
The rapid growth of AI-driven computing has significantly increased the demand for enhanced cooling technologies to manage escalating chip power densities. While two-phase jet impingement cooling shows promising potential for high-flux dissipation, inherent flow instabilities result in pressure oscillations and localized dryout. This study proposes a two-phase jet impingement cooling architecture integrated with a phase separation membrane. Utilizing water as the working fluid and operating at a sub-ambient pressure, the design was successfully implemented and validated on a commercial high-power NVIDIA V100 GPU for the first time. Experimental results show that the GPU core temperature is well controlled below its maximum operating temperature, achieving a thermal resistance of 0.059 K/W at a GPU power of 300 W. Applying phase separation help mitigate the rise in pressure drop with incasing GPU power, maintaining an average reduction of 15.8%. At a GPU power of 293 W, phase separation reduces both pressure drop magnitude and fluctuation to 5.54 kPa and 0.622 kPa, representing a reduction of 13.5% and 16.0%, respectively, compared to the nonseparation case. This work establishes a scalable, high-efficiency thermal management framework for next-generation AI chips.more » « lessFree, publicly-accessible full text available May 26, 2027
An official website of the United States government

Full Text Available