Title: Pressure drop analysis of direct liquid cooled (DLC) rack
This study presents an experimental and numerical characterization of pressure drop in a commercially available direct liquid cooled (DLC) rack. It is important to investigate the pressure drop in the DLC system as it determines the required pumping power for the DLC system, which affects the energy efficiency of the data center. The main objective of this research is to assess the flow rate and pressure distributions in a DLC system to enhance the reliability and the cooling system efficiency. Other objectives of this research are to evaluate the accuracy of flow network modeling (FNM) in predicting the flow distribution in a DLC rack and identify manufacturing limitations in a commercial system that could impact the cooling system reliability. The main components of the investigated DLC system are: coolant distribution module (CDM), supply/return manifold module, and server module which contains a cold plate. Extensive experimental measurements were performed to study the flow distribution and to determine the pressure characteristic curves for the server modules and the coolant distribution module (CDM). Also, a methodology was described to develop an experimentally validated flow network model (FNM) of the DLC system to obtain high accuracy. The measurements revealed a flow maldistribution among the server modules, which is attributed to the manufacturing process of the micro-channel cold plate. The average errors in predicting the flow rate of the server module and the CDM using FNM are 2.5% and 3.8%, respectively. The accuracy and the short run time make FNM a good tool for design, analysis, and optimization for DLC systems. The pressure drop in the server module is found to account for 56% of the total pressure drop in the DLC rack. Further analysis showed that 69% of the pressure drop in the server module is associated with the module's plumbing (corrugated hoses, disconnects, fittings). The server cooling modules are designed to provide secured connections and flexibility, which come with a high pressure drop cost.  more » « less
Award ID(s):
1738793
PAR ID:
10058219
Author(s) / Creator(s):
; ;
Date Published:
Journal Name:
Pressure drop analysis of direct liquid cooled (DLC) rack
Page Range / eLocation ID:
815 to 823
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Abstract Direct Liquid Cooling (DLC) has emerged as a promising technology for thermal management of high-performance computing servers, enabling efficient heat dissipation and reliable operation. Thermal performance is governed by several factors, including the coolant physical properties and flow parameters such as coolant inlet temperature and flow rate. The design and development of the coolant distribution manifold to the Information Technology Equipment (ITE) can significantly impact the overall performance of the computing system. This paper aims to investigate the hydraulic characterization and design validation of a rack-level coolant distribution manifold or rack manifold. To achieve this goal, a custom-built high power-density liquid-cooled ITE rack was assembled, and various cooling loops were plugged into the rack manifold to validate its thermal performance. The rack manifold is responsible for distributing the coolant to each of these cooling loops, which is pumped by a CDU (Coolant Distribution Unit). In this study, pressure drop characteristics of the rack manifold were obtained for flow rates that effectively dissipate the heat loads from the ITE. The pressure drop is a critical parameter in the design of the coolant distribution manifold since it influences the flow rate and ultimately the thermal performance of the system. By measuring the pressure drop at various flow rates, the researchers can accurately determine the optimum flow rate for efficient heat dissipation. Furthermore, 1D flow network and CFD models of the rack-level coolant loop, including the rack manifold, were developed, and validated against experimental test data. The validated models provide a useful tool for the design of facility-level modeling of a liquid-cooled data center. The CFD models enable the researchers to simulate the fluid flow and heat transfer within the cooling system accurately. These models can help to design the coolant distribution manifold at facility level. The results of this study demonstrate the importance of the design and development of the coolant distribution manifold in the thermal performance of a liquid-cooled data center. The study also highlights the usefulness of 1D flow network and CFD models for designing and validating liquid-cooled data center cooling systems. In conclusion, the hydraulic characterization and design validation of a rack-level coolant distribution manifold is critical in achieving efficient thermal management of high-performance computing servers. This study presents a comprehensive approach for hydraulic characterization of the coolant distribution manifold, which can significantly impact the overall thermal performance and reliability of the system. The validated models also provide a useful tool for the design of facility-level modeling of a liquid-cooled data center. 
    more » « less
  2. Miniaturization of microelectronic components comes at a price of high heat flux density. By adopting liquid cooling, the rising demand of high heat flux devices can be met while the reliability of the microelectronic devices can also be improved to a greater extent. Liquid cooled cold plates are largely replacing air based heat sinks for electronics in data center applications, thanks to its large heat carrying capacity. A bench level study was carried out to characterize the thermohydraulic performance of two microchannel cold plates which uses warm DI water for cooling Multi Chip Server Modules (MCM). A laboratory built mock package housing mock dies and a heat spreader was employed while assessing the thermal performance of two different cold plate designs at varying coolant flow rate and temperature. The case temperature measured at the heat spreader for varying flow rates and input power were essential in identifying the convective resistance. The flow performance was evaluated by measuring the pressure drop across cold plate module at varying flow rates. Cold plate with the enhanced microchannel design yielded better results compared to a traditional parallel microchannel design. The study conducted at higher coolant temperatures yielded lower pressure drop values with no apparent change in the thermal behavior using different cold plates. The tests conducted after reversing the flow direction in microchannels provide an insight at the effect of neighboring dies on each other and reveal the importance of package specific cold plate designs for top performance. The experimental results were validated using a numerical model which are further optimized for improved geometric designs. 
    more » « less
  3. Recent commercial efforts have reestablished the benefits of cooling server modules using direct liquid cooling (DLC) technology. The primary drivers behind this technology are the increase in chip densities and the absolute need to reduce the overall data center power usage. In DLC technology, a cold plate is situated on top of the chip with thermal interface material between the chip and the cold plate. The low thermal resistance path facilitates the use of warm water which helps data centers in replacing the chilled water system by a water side economizer utilizing ambient temperature. This work describes the effort to leverage DLC by employing microchannel cold plates to cool multi-chip modules. The primary objective of this work is to build a sophisticated test rig to characterize the flow and thermal performance of a microchannel cold plate for cooling a two-die chip. This study highlights the challenges of building an experimental setup which simulates a two-die chip package and the approaches taken to overcome the challenges. A parallel channel cold plate is used to benchmark the performance. Tests were conducted for a set of independent variables like flow rate, input power to dice, coolant temperature, flow direction and TIM resistance. The results are presented as PQ curves, specific thermal resistance curves and case temperature distribution reflecting the effect of changing the input variables. 
    more » « less
  4. Abstract Demand is growing for the dense and high-performing IT computing capacity to support artificial intelligence, deep learning, machine learning, autonomous cars, the Internet of Things, etc. This led to an unprecedented growth in transistor density for high-end CPUs and GPUs, creating thermal design power (TDP) of even more than 700 watts for some of the NVIDIA existing GPUs. Cooling these high TDP chips with air cooling comes with a cost of the higher form factor of servers and noise produced by server fans close to the permissible limit. Direct-to-chip cold plate-based liquid cooling is highly efficient and becoming more reliable as the advancement in technology is taking place. Several components are used in the liquid-cooled data centers for the deployment of cold plate-based direct-to-chip liquid cooling like cooling loops, rack manifolds, CDUs, row manifolds, quick disconnects, flow control valves, etc. Row manifolds used in liquid cooling are used to distribute secondary coolant to the rack manifolds. Characterizing these row manifolds to understand the pressure drops and flow distribution for better data center design and energy efficiency is important. In this paper, the methodology is developed to characterize the row manifolds. Water-based coolant Propylene glycol 25% was used as the coolant for the experiments and experiments were conducted at 21 °C coolant supply temperature. Two, six-port row manifolds' P-Q curves were generated, and the value of supply pressure and the flowrate were measured at each port. The results obtained from the experiments were validated by a technique called flow network modeling (FNM). FNM technique uses the overall flow and thermal characteristics to represent the behavior of individual components. 
    more » « less
  5. Abstract Due to the increasing computational demand driven by artificial intelligence, machine learning, and the Internet of Things (IoT), there has been an unprecedented growth in transistor density for high-end CPUs and GPUs. This growth has resulted in high thermal dissipation power (TDP) and high heat flux, necessitating the adoption of advanced cooling technologies to minimize thermal resistance and optimize cooling efficiency. Among these technologies, direct-to-chip cold plate-based liquid cooling has emerged as a preferred choice in electronics cooling due to its efficiency and cost-effectiveness. In this context, different types of single-phase liquid coolants, such as propylene glycol (PG), ethylene glycol (EG), DI water, treated water, and nanofluids, have been utilized in the market. These coolants, manufactured by different companies, incorporate various inhibitors and chemicals to enhance long-term performance, prevent biogrowth, and provide corrosion resistance. However, the additives used in these coolants can impact their thermal performance, even when the base coolant is the same. This paper aims to compare these coolant types and evaluate the performance of the same coolant from different vendors. The selection of coolants in this study is based on their performance, compatibility with wetted materials, reliability during extended operation, and environmental impact, following the guidelines set by ASHRAE. To conduct the experiments, a single cold plate-based benchtop setup was constructed, utilizing a thermal test vehicle (TTV), pump, reservoir, flow sensor, pressure sensors, thermocouple, data acquisition units, and heat exchanger. Each coolant was tested using a dedicated cold plate, and thorough cleaning procedures were carried out before each experiment. The experiments were conducted under consistent boundary conditions, with a TTV power of 1000 watts and varying coolant flow rates (ranging from 0.5 lpm to 2 lpm) and supply coolant temperatures (17°C, 25°C, 35°C, and 45°C), simulating warm water cooling. The thermal resistance (Rth) versus flow rate and pressure drop (ΔP) versus flow rate graphs were obtained for each coolant, and the impact of different supply coolant temperatures on pressure drop was characterized. The data collected from this study will be utilized to calculate the Total Cost of Ownership (TCO) in future research, providing insights into the impact of coolant selection at the data center level. There is limited research available on the reliability used in direct-to-chip liquid cooling, and there is currently no standardized methodology for testing their reliability. This study aims to fill this gap by focusing on the reliability of coolants, specifically propylene glycols at concentrations of 25%. To analyze the effectiveness of corrosion inhibitors in these coolants, ASTM standard D1384 apparatus, typically used for testing engine coolant corrosion inhibitors on metal samples in controlled laboratory settings, was employed. The setup involved immersing samples of wetted materials (copper, solder coated brass, brass, steel, cast iron, and cast aluminum) in separate jars containing inhibited propylene glycol solutions from different vendors. This test will determine the reliability difference between the same inhibited solutions from different vendors. 
    more » « less