Title: Pressure drop analysis of direct liquid cooled (DLC) rack
This study presents an experimental and numerical characterization of pressure drop in a commercially available direct liquid cooled (DLC) rack. It is important to investigate the pressure drop in the DLC system as it determines the required pumping power for the DLC system, which affects the energy efficiency of the data center. The main objective of this research is to assess the flow rate and pressure distributions in a DLC system to enhance the reliability and the cooling system efficiency. Other objectives of this research are to evaluate the accuracy of flow network modeling (FNM) in predicting the flow distribution in a DLC rack and identify manufacturing limitations in a commercial system that could impact the cooling system reliability. The main components of the investigated DLC system are: coolant distribution module (CDM), supply/return manifold module, and server module which contains a cold plate. Extensive experimental measurements were performed to study the flow distribution and to determine the pressure characteristic curves for the server modules and the coolant distribution module (CDM). Also, a methodology was described to develop an experimentally validated flow network model (FNM) of the DLC system to obtain high accuracy. The measurements revealed a flow maldistribution among the server modules, which is attributed to the manufacturing process of the micro-channel cold plate. The average errors in predicting the flow rate of the server module and the CDM using FNM are 2.5% and 3.8%, respectively. The accuracy and the short run time make FNM a good tool for design, analysis, and optimization for DLC systems. The pressure drop in the server module is found to account for 56% of the total pressure drop in the DLC rack. Further analysis showed that 69% of the pressure drop in the server module is associated with the module's plumbing (corrugated hoses, disconnects, fittings). The server cooling modules are designed to provide secured connections and flexibility, which come with a high pressure drop cost.  more » « less
Award ID(s):
1738793
NSF-PAR ID:
10058219
Author(s) / Creator(s):
; ;
Date Published:
Journal Name:
Pressure drop analysis of direct liquid cooled (DLC) rack
Page Range / eLocation ID:
815 to 823
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Miniaturization of microelectronic components comes at a price of high heat flux density. By adopting liquid cooling, the rising demand of high heat flux devices can be met while the reliability of the microelectronic devices can also be improved to a greater extent. Liquid cooled cold plates are largely replacing air based heat sinks for electronics in data center applications, thanks to its large heat carrying capacity. A bench level study was carried out to characterize the thermohydraulic performance of two microchannel cold plates which uses warm DI water for cooling Multi Chip Server Modules (MCM). A laboratory built mock package housing mock dies and a heat spreader was employed while assessing the thermal performance of two different cold plate designs at varying coolant flow rate and temperature. The case temperature measured at the heat spreader for varying flow rates and input power were essential in identifying the convective resistance. The flow performance was evaluated by measuring the pressure drop across cold plate module at varying flow rates. Cold plate with the enhanced microchannel design yielded better results compared to a traditional parallel microchannel design. The study conducted at higher coolant temperatures yielded lower pressure drop values with no apparent change in the thermal behavior using different cold plates. The tests conducted after reversing the flow direction in microchannels provide an insight at the effect of neighboring dies on each other and reveal the importance of package specific cold plate designs for top performance. The experimental results were validated using a numerical model which are further optimized for improved geometric designs. 
    more » « less
  2. Recent commercial efforts have reestablished the benefits of cooling server modules using direct liquid cooling (DLC) technology. The primary drivers behind this technology are the increase in chip densities and the absolute need to reduce the overall data center power usage. In DLC technology, a cold plate is situated on top of the chip with thermal interface material between the chip and the cold plate. The low thermal resistance path facilitates the use of warm water which helps data centers in replacing the chilled water system by a water side economizer utilizing ambient temperature. This work describes the effort to leverage DLC by employing microchannel cold plates to cool multi-chip modules. The primary objective of this work is to build a sophisticated test rig to characterize the flow and thermal performance of a microchannel cold plate for cooling a two-die chip. This study highlights the challenges of building an experimental setup which simulates a two-die chip package and the approaches taken to overcome the challenges. A parallel channel cold plate is used to benchmark the performance. Tests were conducted for a set of independent variables like flow rate, input power to dice, coolant temperature, flow direction and TIM resistance. The results are presented as PQ curves, specific thermal resistance curves and case temperature distribution reflecting the effect of changing the input variables. 
    more » « less
  3. Abstract Transistor density trends till recently have been following Moore's law, doubling every generation resulting in increased power density. The computational performance gains with the breakdown of Moore's law were achieved by using multicore processors, leading to nonuniform power distribution and localized high temperatures making thermal management even more challenging. Cold plate-based liquid cooling has proven to be one of the most efficient technologies in overcoming these thermal management issues. Traditional liquid-cooled data center deployments provide a constant flow rate to servers irrespective of the workload, leading to excessive consumption of coolant pumping power. Therefore, a further enhancement in the efficiency of implementation of liquid cooling in data centers is possible. The present investigation proposes the implementation of dynamic cooling using an active flow control device to regulate the coolant flow rates at the server level. This device can aid in pumping power savings by controlling the flow rates based on server utilization. The flow control device design contains a V-cut ball valve connected to a microservo motor used for varying the device valve angle. The valve position was varied to change the flow rate through the valve by servomotor actuation based on predecided rotational angles. The device operation was characterized by quantifying the flow rates and pressure drop across the device by changing the valve position using both computational fluid dynamics and experiments. The proposed flow control device was able to vary the flow rate between 0.09 lpm and 4 lpm at different valve positions. 
    more » « less
  4. null (Ed.)
    Abstract Data centers are a large group of networked servers used by organizations for computational and storage purposes. In 2014, data centers consumed an estimated 70 billion kWh in the United States alone. It is incumbent on thermal engineers to develop efficient methods in order to minimize the expenditure at least toward cooling considering the limited available power resources. One of the key areas where electronic cooling research has been focusing, is addressing the issue of nonuniform power distribution at the rack, server and even at package levels. Nonuniform heating at the chip level creates hotspots and temperature gradients across the chip which in turn significantly increases the cost of cooling, as cooling cost is a function of the maximum junction temperature. This challenge has increased the use of temperature sensing mechanisms to help in finding ways to mitigate the gradients. A very effective way to conserve pumping power and address hotspots on the single or multichip modules is by targeted delivery of liquid coolant. One way to enable such targeted delivery of coolant is by using dynamic cold plates coupled with self-regulating flow control device that can control flow rate based on temperature. This novel technology will have more effective implementation coupled with a good control strategy. This paper addresses the development and testing of such control strategy with minimal sensors along with less latency and optimization of the same. 
    more » « less
  5. Miniaturization and high heat flux of power electronic devices have posed a colossal challenge for adequate thermal management. Conventional air-cooling solutions are inadequate for high-performance electronics. Liquid cooling is an alternative solution thanks to the higher specific heat and latent heat associated with the coolants. Liquid-cooled cold plates are typically manufactured by different approaches such as: skived, forged, extrusion, electrical discharge machining. When researchers are facing challenges at creating complex geometries in small spaces, 3D-printing can be a solution. In this paper, a 3D-printed cold plate was designed and characterized with water coolant. The printed metal fin structures were strong enough to undergo pressure from the fluid flow even at high flow rates and small fin structures. A copper block with top surface area of 1 inch by 1 inch was used to mimic a computer chip. Experimental data has good match with a simulation model which was built using commercial software 6SigmaET. Effects of geometry parameters and operating parameters were investigated. Fin diameter was varied from 0.3 mm to 0.5 mm and fin height was maintained at 2 mm. A special manifold was designed to maximize the surface contact area between coolant and metal surface and therefore minimize thermal resistance. The flow rate was varied from 0.75 L/min to 2 L/min and coolant inlet temperature was varied from 25 to 48 oC. It was observed that for the coolant inlet temperature 25 oC and aluminum cold plate, the junction temperature was kept below 63.2 oC at input power 350 W and pressure drop did not exceed 23 Kpa. Effects of metal materials used in 3D-printing on the thermal performance of the cold plate were also studied in detail. 
    more » « less