Title: An Experimental Analysis of Hot Aisle Containment Systems
In recent years, various airflow containment systems have been deployed in data centers to improve the cooling efficiency by minimizing the mixing of hot and cold air streams. The goal of this study is the experimental investigation of passive and active hot aisle containment (HAC) systems. Also investigated, will be the dynamic interaction between HAC and information technology equipment (ITE). In addition, various provisioning levels of HAC are studied. In this study, a chimney exhaust rack (CER) is considered as the HAC system. The rack is populated by 22 commercial 2-RU servers and one network switch. Four scenarios with and without the presence of cold and hot aisle containments are investigated and compared. The transient pressure build-up inside the rack, servers' fan speed, inlet air temperatures (IAT), IT power consumption, and CPU temperatures are monitored and operating data recorded. In addition, IAT of selected servers is measured using external temperature sensors and compared with data available via the Intelligent Platform Management Interface (IPMI). To the best of authors' knowledge, this is the first experimental study in which a HAC system is analyzed using commercial ITE in a white space. It is observed that presence of backpressure can lead to a false high IPMI IAT reading. Consequently, a cascade rise in servers' fan speed is observed, which increases the backpressure and worsen the situation. As a result, the thermal performance of ITE and power consumption of the rack are affected. Furthermore, it is shown that the backpressure can affect the accuracy of common data center efficiency metrics.  more » « less
Award ID(s):
1134867
NSF-PAR ID:
10074942
Author(s) / Creator(s):
; ; ; ;
Date Published:
Journal Name:
2018 17th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)
Page Range / eLocation ID:
748 to 760
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. There are various designs for segregating hot and cold air in data centers such as cold aisle containment (CAC), hot aisle containment (HAC), and chimney exhaust rack. These containment systems have different characteristics and impose various conditions on the information technology equipment (ITE). One common issue in HAC systems is the pressure buildup inside the HAC (known as backpressure). Backpressure also can be present in CAC systems in case of airflow imbalances. Hot air recirculation, limited cooling airflow rate in servers, and reversed flow through ITE with weaker fan systems (e.g. network switches) are some known consequences of backpressure. Currently there is a lack of experimental data on the interdependency between overall performance of ITE and its internal design when a backpressure is imposed on ITE. In this paper, three commercial 2-rack unit (RU) servers with different internal designs from various generations and performance levels are tested and analyzed under various environmental conditions. Smoke tests and thermal imaging are implemented to study the airflow patterns inside the tested equipment. In addition, the impact leak of hot air into ITE on the fan speed and the power consumption of ITE is studied. Furthermore, the cause of the discrepancy between measured inlet temperatures by internal intelligent platform management interface (IPMI) and external sensors is investigated. It is found that arrangement of fans, segregation of space upstream and downstream of fans, leakage paths, location of sensors of baseboard management controller (BMC) and presence of backpressure can have a significant impact on ITE power and cooling efficiency. 
    more » « less
  2. Most of the thermal management technologies concentrate on managing airflow to achieve the desired server inlet temperature (supply air operating set point) and not to manage/improve the amount of cool air (CFM) that each computer rack (i.e. IT servers) should receive in order to remove the produced heat. However, airflow is equally important for quantifying adequate cooling to IT equipment, but it is more challenging to obtain a uniform airflow distribution at the inlet of computer racks. Therefore, as a potential option for improving airflow distribution is to eliminate the sources of non-uniformities such as maldistribution of under-floor plenum pressure field caused by vortices. Numerous researchers focus on the adverse effects of under-floor blockages. This study focused to numerically investigate the positive impact of selectively placed obstructions (on-purpose air-directors); referred as partitions; Quantitative and qualitative analysis of underfloor plenum pressure field, perforated tiles airflow rate and racks inlet temperature with and without partitions using two Computational Fluid Dynamics (CFD) models, which were built using Future Facilities 6SigmaRoom CFD tool. First, a simple data center model was used to quantify the partitions benefits for two different systems; Hot Aisle Containment (HAC) compared to an open configuration. Second, the investigation was expanded using a physics-based experimentally validated CFD model of medium size data center (more complicated data center geometry) to compare different types of proposed partitions. Both models results showed that partition type I (partitions height of $\frac{2}{3}$ of plenum depth measured from the subfloor) eliminates the presence of vortices in the under-floor plenum and hence, more uniform pressure differential across the perforated tiles that drives more uniform airflow rates. In addition, the influence of proposed partitions on the rack inlet temperature was reported through a comparison between open versus hot aisle containment. The results showed that the partitions have a minor effect on the rack inlet temperature for the hot aisle containment system. However, the partitions significantly improve the tiles flowrate. On the other hand, for the open system, the presence of partitions has improved the tiles airflow rate, rack inlet temperature and hence eliminate the hot spots formation at computer rack inlet 
    more » « less
  3. The most common approach to air cooling of data centers involves the pressurization of the plenum beneath the raised floor and delivery of air flow to racks via perforated floor tiles. This cooling approach is thermodynamically inefficient due in large part to the pressure losses through the tiles. Furthermore, it is difficult to control flow at the aisle and rack level since the flow source is centralized rather than distributed. Distributed cooling systems are more closely coupled to the heat generating racks. In overhead cooling systems, one can distribute flow to distinct aisles by placing the air mover and water cooled heat exchanger directly above an aisle. Two arrangements are possible: (i.) placing the air mover and heat exchanger above the cold aisle and forcing downward flow of cooled air into the cold aisle (Overhead Downward Flow (ODF)), or (ii.) placing the air mover and heat exchanger above the hot aisle and forcing heated air upwards from the hot aisle through the water cooled heat exchanger (Overhead Upward Flow (OUF)). This study focuses on the steady and transient behavior of overhead cooling systems in both ODF and OUF configurations and compares their cooling effectiveness and energy efficiency. The flow and heat transfer inside the servers and heat exchangers are modeled using physics based approaches that result in differential equation based mathematical descriptions. These models are programmed in the MATLAB™ language and embedded within a CFD computational environment (using the commercial code FLUENT™) that computes the steady or instantaneous airflow distribution. The complete computational model is able to simulate the complete flow and thermal field in the airside, the instantaneous temperatures within and pressure drops through the servers, and the instantaneous temperatures within and pressure drops through the overhead cooling system. Instantaneous overall energy consumption (1st Law) and exergy destruction (2nd Law) were used to quantify overall energy efficiency and to identify inefficiencies within the two systems. The server cooling effectiveness, based on an effectiveness-NTU model for the servers, was used to assess the cooling effectiveness of the two overhead cooling approaches 
    more » « less
  4. Data centers house a variety of compute, storage, network IT hardware where equipment reliability is of utmost importance. Heat generated by the IT equipment can substantially reduce its service life if Tjmax, maximum temperature that the microelectronic device tolerates to guarantee reliable operation, is exceeded. Hence, data center rooms are bound to maintain continuous conditioning of the cooling medium becoming large energy consumers. The objective of this work is to introduce and evaluate a new end-of-aisle cooling design which consists of three cooling configurations. The key objectives of close-coupled cooling are to enable a controlled cooling of the IT equipment, flexible as well as modular design, and containment of hot air exhaust from the cold air. The thermal performance of the proposed solution is evaluated using CFD modeling. A computational model of a small size data center room has been developed. Larger axial fans are selected and placed at rack-level which constitute the rack-fan wall design. The model consists of 10 electronic racks each dissipating a heat load of 8kw. The room is modeled to be hot aisle containment i.e. the hot air exhaust exiting for each row is contained and directed within a specific volume. Each rack has passive IT with no server fans and the servers are cooled by means of rack fan wall. The cold aisle is separated with hot aisle by means of banks of heat exchangers placed on the either sides of the aisle containment. Based on the placement of rack fans, the design is divided to three sub designs — case 1: passive heat exchangers with rack fan walls; case 2: active heat exchangers (HXs coupled with fans) with rack fan walls; case 3: active heat exchangers (hxs coupled with fans) with no rack fans. The cooling performance is calculated based on the thermal and flow parameters obtained for all three configurations. The computational data obtained has shown that the case 1 is used only for lower system resistance IT. However, case 2 and Case 3 can handle denser IT systems. Case 3 is the design that can consume lower fan energy as well as handle denser IT systems. The paper also discusses the cooling behavior of each type of design. 
    more » « less
  5. Given the vital rule of data center availability and since the inlet temperature of the IT equipment increase rapidly until reaching a certain threshold value after which IT starts throttling or shut down because of overheat during cooling system failure. Hence, it is especially important to understand failures and their effects. This study presented experimental investigation and analysis of a facility-level cooling system failure scenario in which chilled water interruption introduced to the data center. Quantitative instrumentation tools including wireless technology such as wireless temperature and pressure sensors were used to measure the discrete air inlet temperature and pressure differential though cold aisle enclosure, respectively. In addition, Intelligent Platform Management Interface (IPMI) and cooling system data during failure/recovery were reported. Furthermore, the IT equipment performance and response for opened and contained environments were simulated and compared. Finally, an experiment based analysis of the Ride Through Time (RTT) of servers during chilled water interruption of the cooling infrastructure presented as well. The results showed that for all three classes of servers tested during the cooling failure, CAC helped keep the server’s cooler for longer. The containment provided a barrier between the hot and cold air streams and caused slight negative pressure to build up, which allowed the servers to pull cold air from the underfloor plenum. In addition, the results show that the effect of CAC in containment solutions on the IT equipment performance and response could vary and depend on the server’s airflow, generation and hence types of servers deployed in cold aisle enclosure. Moreover, it was shown that when compared to the discrete sensors, the IPMI inlet temperature sensors underestimate the Ride Through Time (RTT) by 42% and 12% for the CAC and opened cases, respectively. 
    more » « less