The objective of this work is to introduce the application of an artificial neural network (ANN) to assist in the evaporative cooling in data centers. To achieve this task, we employ the neural network algorithms to predict weather conditions outside the data center for direct evaporative cooling (DEC) operations. The predictive analysis helps optimize the cooling control strategy for maximizing the usage of evaporative cooling thereby improving the efficiency of the overall data center cooling system. A typical artificial neural network architecture is dynamic in nature and can perform adaptive learning in minimal computation time. A neural network model of a data center was created using operational historical data collected from a data center cooling control system. The neural network model allows the control of the modular data center (MDC) cooling at optimum configuration in two ways. First way is that the network model minimizes time delay for switching the cooling from one mode to the other. Second way, it improves the reaction behavior of the cooling equipment if an unexpected ambient condition change should come. The data center in consideration is a test bed modular data center that comprises of information Technology (IT) racks, Direct Evaporative cooling (DEC) and Indirect Evaporative Cooling (IEC) modules; the DEC/IEC are used together or in alternative mode to cool the data center room. The facility essentially utilizes outside ambient temperature and humidity conditions that are further conditioned by the DEC and IEC to cool the electronics, a concept know as air-side economization. Various parameters are related to the cooling system operation such as outside air temperature, IT heat load, cold aisle temperature, cold aisle humidity etc. are considered. Some of these parameters are fed into the artificial neural network as inputs and some are set as targets to train the neural network system. After the training the process is completed, certain bucket of data is tested and further used to validate the outputs for various other weather conditions. To make sure the analysis represents real world scenario, the operational data used are from real time data logged on the MDC cooling control unit. Overall, the neural network model is trained and is used to successfully predict the weather conditions and cooling control parameters. The prediction models have been demonstrated for the outputs that are static in nature (Levenberg Marquardt method) as well as the outputs that are dynamic in nature i.e., step-ahead & multistep ahead techniques.
more »
« less
Neural Network Based Bin Analysis for Indirect/Direct Evaporative Cooling of Modular Data Centers
With an increase in the need for energy efficient data centers, a lot of research is being done to maximize the use of Air Side Economizers (ASEs), Direct Evaporative Cooling (DEC), Indirect Evaporative Cooling (IEC) and multistage Indirect/Direct Evaporative Cooling (I/DEC). The selection of cooling configurations installed in modular cooling units is based on empirical/analytical studies and domain knowledge that fail to account for the nonlinearities present in an operational data center. In addition to the ambient conditions, the attainable cold aisle temperature and humidity is also a function of the control strategy and the cooling setpoints in the data center.The primary objective of this study is to use Artificial Neural Network (ANN) modelling and Psychrometric bin analysis to assess the applicability of various cooling modes to a climatic condition. Training dataset for the ANN model is logged from the monitoring sensor array of a modular data center laboratory with an I/DEC module. The data-driven ANN model is utilized for predicting the cold aisle humidity and temperatures for different modes of cooling. Based on the predicted cold aisle temperature and humidity, cold aisle envelopes are represented on a psychrometric chart to evaluate the applicability of each cooling mode to the territorial climatic condition. Subsequently, outside air conditions favorable to each cooling mode in achieving cold aisle conditions, within the ASHRAE recommended environmental envelope, is also visualized on a psychrometric chart. Control strategies and opportunities to optimize the cooling system are discussed.
more »
« less
- Award ID(s):
- 1738811
- PAR ID:
- 10100239
- Date Published:
- Journal Name:
- Proceedings of the ASME 2018 International Mechanical Engineering Congress and Exposition
- Page Range / eLocation ID:
- V06AT08A053
- Format(s):
- Medium: X
- Sponsoring Org:
- National Science Foundation
More Like this
-
-
The objective of this work is to introduce and evaluate a new end-of-aisle cooling design which consists of three cooling configurations. The key objectives of close-coupled cooling are to enable controlled cooling of information technology (IT) equipment, flexible and modular design, and the containment of hot air exhaust from the cold air. The thermal performance of the proposed solution is evaluated using computational fluid dynamics modeling. A computational model of a small size data center room has been developed. The room is modeled to be a hot aisle containment setup, i.e., the hot air exhaust exiting for each row is contained and directed within a specific volume. The cold aisle is separated from the hot aisle by means of banks of heat exchangers (HXs) placed on either side of the containment aisle. Based on the placement of rack fans, the design is divided into three sub-designs—Case 1: passive HXs with rack fan walls; Case 2: active HXs (coupled with fans) with rack fan walls; Case 3: active HXs (coupled with fans) with no rack fans. The cooling performance is calculated based on the thermal and flow parameters obtained for all three configurations. The computational data obtained has shown that the Case 1 is used only for lower system resistance IT. However, Cases 2 and 3 can handle denser IT systems. Case 3 is the design that can consume lower fan energy and handle denser IT systems. The article also discusses the cooling behavior of each type of design under cooling failure conditions with Case 2 showing better cooling redundancy compared with other two cases.more » « less
-
Data centers house a variety of compute, storage, network IT hardware where equipment reliability is of utmost importance. Heat generated by the IT equipment can substantially reduce its service life if Tjmax, maximum temperature that the microelectronic device tolerates to guarantee reliable operation, is exceeded. Hence, data center rooms are bound to maintain continuous conditioning of the cooling medium becoming large energy consumers. The objective of this work is to introduce and evaluate a new end-of-aisle cooling design which consists of three cooling configurations. The key objectives of close-coupled cooling are to enable a controlled cooling of the IT equipment, flexible as well as modular design, and containment of hot air exhaust from the cold air. The thermal performance of the proposed solution is evaluated using CFD modeling. A computational model of a small size data center room has been developed. Larger axial fans are selected and placed at rack-level which constitute the rack-fan wall design. The model consists of 10 electronic racks each dissipating a heat load of 8kw. The room is modeled to be hot aisle containment i.e. the hot air exhaust exiting for each row is contained and directed within a specific volume. Each rack has passive IT with no server fans and the servers are cooled by means of rack fan wall. The cold aisle is separated with hot aisle by means of banks of heat exchangers placed on the either sides of the aisle containment. Based on the placement of rack fans, the design is divided to three sub designs — case 1: passive heat exchangers with rack fan walls; case 2: active heat exchangers (HXs coupled with fans) with rack fan walls; case 3: active heat exchangers (hxs coupled with fans) with no rack fans. The cooling performance is calculated based on the thermal and flow parameters obtained for all three configurations. The computational data obtained has shown that the case 1 is used only for lower system resistance IT. However, case 2 and Case 3 can handle denser IT systems. Case 3 is the design that can consume lower fan energy as well as handle denser IT systems. The paper also discusses the cooling behavior of each type of design.more » « less
-
Owing to the dramatic increase in IT power density and energy consumption, the data center (DC) sector has started adopting thermally- and energy-efficient liquid cooling methods. This study examines a single-phase direct-to-chip liquid cooling approach for three high-heat-density racks, utilizing two liquid-to-air (L2A) cooled coolant distribution units (CDUs) and a combined total heat load of 128 kW. An experimental setup was developed to test different types of CDUs, cooling loops, and thermal testing vehicles (TTVs) for different operating conditions. IR images and the collected data were used to investigate the effect of air recirculation between cold and hot aisle containments on the CDU’s performance and stability of supply air temperature (SAT). Three different types of cooling loops (X, Y, and Z) were characterized thermally and hydraulically. Results show that Type Y has the lowest cold plate thermal resistance and pressure drop, among others. In a later test that included a single rack at a heat load of 53 kW and a single CDU, the heat capture ratio for fluid was found to be 94%. Experiments show that using blanking panels on the back of the racks limits hot air recirculation and maintains a steady SAT in the cold aisle. Finally, the CDU performance was evaluated at a high heat load for the three racks at 128 kW, and the average cooling capacity of the units is 58.6 kW, and the effectiveness values for CDU 1 and CDU 2 are 0.83 and 0.82, respectively.more » « less
-
The dynamic nature of today’s data centers requires active monitoring and holistic management of all aspects of the facility, from the applications to the air conditioning. The most significant aspect of implementing a dynamic data center is the requirement to actively monitor and manage the infrastructure assets. It is vital to ensure information technology (IT) equipment has access to sufficient air (provisioned) at a proper temperature to assure their optimal and continues operation. Hot air recirculation, elevated fan speed, and hot spots are known consequences of an under-provisioned cold aisle. On the other hand, over-provisioning a cold aisle can lead to a significant loss in energy due to bypass of cooling air and leakages. Besides, the number of active servers in an aisle may be varied by load balancers due to short or long-term IT load changes. This demonstrates the need for an active airflow management scheme that is able to respond to airflow demand in different aisles of a data center. In this study, remotely controllable air dampers are implemented to regulate airflow delivery to a cold aisle containment (CAC) during workload changes in a data center. The energy saving opportunities are investigated and practical considerations are discussed.more » « less
An official website of the United States government