Title: Transient angle stability of inverters equipped with robust droop control
Transient angle stability of inverters equipped with the robust droop controller is investigated in this work. At first, the conditions on the control references to guarantee the existence of a feasible post-disturbance operating point are derived. Then, the post-disturbance equilibrium points are found and their stability properties are characterized. Furthermore, the attraction regions of the stable equilibrium points are accurately depicted by calculating the stable and unstable manifolds of the surrounding unstable equilibrium points, which presents an explanation to system transient stability. Finally, the transient control considerations are provided to help the inverter ride-through the disturbance and maintain its stability characteristics. It is shown that the transient angle stability is not a serious problem for droop controlled inverters with proper control settings.  more » « less
Award ID(s):
1810105
PAR ID:
10427619
Author(s) / Creator(s):
; ; ; ;
Date Published:
Journal Name:
CSEE Journal of Power and Energy Systems
ISSN:
2096-0042
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. This paper proposed an energy function-embedded quasi-steady-state model for efficient simulation of cascading outages on a power grid while addressing transient stability concerns. Compared to quasi-steady-state models, the proposed model incorporates short-term dynamic simulation and an energy function method to efficiently evaluate the transient stability of a power grid together with outage propagation without transient stability simulation. Cascading outage simulation using the proposed model conducts three steps for each disturbance such as a line outage. First, it performs time-domain simulation for a short term to obtain a post-disturbance trajectory. Second, along the trajectory, the system state with the local maximum potential energy is found and used as the initial point to search for a relevant unstable equilibrium by Newton's method. Third, the transient energy margin is estimated based on this unstable equilibrium to predict an out-of-step condition with generators. The proposed energy function-embedded quasi-steady-state model is tested in terms of its accuracy and time performance on an NPCC 140-bus power system and compared to a quasi-steady-state model embedding transient stability simulation. 
    more » « less
  2. This paper proposes a control scheme that prevents the adverse dynamic interactions between the heterogeneously controlled grid-forming inverters (GFMI) in power electronics dominated grid (PEDG) towards a resilient self-driving grid. The primary controller of GFMIs in a grid cluster can vary based on their manufacturers such as virtual synchronous generation, droop control, power synchronization control, etc. Therefore, this can introduce heterogeneity among the network of GFMIs in PEDG. Resultantly, during the interconnection of GFMIs that are based on heterogenous primary controller poses various synchronization and dynamic interaction challenges in PEDG. For instance, severe fluctuations in frequency and voltage, high ROCOF, unintended reactive power circulation that poses a threat on the overall transient stability of the PEDG. Therefore, to mitigate these adverse dynamic interactions among the heterogeneously controlled GFMIs, a force enclaved homogenization (FEH) control is proposed in a supervisory level controller. This will autonomously adjust inertia coefficients of the each GFMI to have homogenous transient response and will enforce coherency among the heterogenous DGs. This will prevent the PEDG from the adverse dynamic interactions during an interconnection and load disturbance. Various case studies are presented that validates the effectiveness of the proposed FEH control. 
    more » « less
  3. Microgrids must be able to restore voltage and frequency to their reference values during transient events; inverters are used as part of a microgrid's hierarchical control for maintaining power quality. Reviewed methods either do not allow for intuitive trade-off tuning between the objectives of synchronous state restoration, local reference tracking, and disturbance rejection, or do not consider all of these objectives. In this paper, we address all of these objectives for voltage restoration in droop-controlled inverter-based islanded micro-grids. By using distributed model predictive control (DMPC) in series with an unscented Kalman Filter (UKF), we design a secondary voltage controller to restore the voltage to the reference in finite time. The DMPC solves a reference tracking problem while rejecting reactive power disturbances in a noisy system. The method we present accounts for non-zero mean disturbances by design of a random-walk estimator. We validate the method's ability to restore the voltage in finite time via modeling a multi-node microgrid in Simulink. 
    more » « less
  4. This paper characterizes synchronization perfor- mance and total transient power losses in droop-controlled microgrids with heterogeneously rated inverters. We consider frequency and voltage dynamics for a Kron-reduced network model with highly inductive lines in the presence of impulse disturbances. We quantify the total transient frequency and voltage deviations from synchrony and the associated total transient resistive losses through the L 2 norm of the system output. We derive closed-form expressions for this norm that depend on the heterogeneous droop gains and properties of the network. Our results indicate the importance of inertia in mitigating transient frequency deviations. We also show that if disturbances are uniform, the transient resistive losses are given by a monotonically decreasing function of the active power droop gains regardless of the network topology. Numerical examples further analyze these losses, revealing that they can be amplified by high droop gain heterogeneity. This relationship indicates that non-uniform power sharing requirements can limit performance. 
    more » « less
  5. This paper investigates the dynamics of systemic risk in banking networks by analyzing equilibrium points and stability conditions. The focus is on a model that incorporates interactions among distressed and undistressed banks. The equilibrium points are determined by solving a reduced system of equations, considering both homogeneous and heterogeneous scenarios. Local and global stability analyses reveal conditions under which equilibrium points are stable or unstable. Numerical simulations further illustrate the dynamics of systemic risk, while the theoretical findings offer insights into the behavior of distressed banks under varying conditions. Overall, the model enhances our understanding of systemic financial risk and offers valuable insights for risk management and policymaking in the banking sector. 