skip to main content


Title: Frequency regulation for microgrid using genetic algorithm and particle swarm optimization tuned STATCOM
Abstract

This paper presents the genetic algorithm (GA) and particle swarm optimization (PSO) based frequency regulation for a wind‐based microgrid (MG) using reactive power balance loop. MG, operating from squirrel cage induction generator (SCIG), is employed for exporting the electrical power from wind turbines, and it needs reactive power which may be imported from the grid. Additional reactive power is also required from the grid for the load, directly coupled with such a distributed generator (DG) plant. However, guidelines issued by electric authorities encourage MGs to arrange their own reactive power because such reactive power procurement is defined as a local area problem for power system studies. Despite the higher cost of compensation, static synchronous compensator (STATCOM) is a fast‐acting FACTs device for attending to these reactive power mismatches. Reactive power control can be achieved by controlling reactive current through the STATCOM. This can be achieved with modification in current controller scheme of STATCOM. STATCOM current controller is designed with reactive power load balance for the proposed microgrid in this paper. Further, gain values of the PI controller, required in the STATCOM model, are selected first with classical methods. In this classical method, iterative procedures which are based on integral square error (ISE), integral absolute error (IAE), and integral square of time error (ISTE) criteria are developed using MATLAB programs. System performances are further investigated with GA and PSO based control techniques and their acceptability over classical methods is diagnosed. Results in terms of converter frequency deviation show how the frequency remains under the operating boundaries as allowed by IEEE standards 1159:1995 and 1250:2011 for integrating renewable‐based microgrid with grid. Real and reactive power management and load current total harmonic distortions verify the STATCOM performance in MG. The results are further validated with the help of recent papers in which frequency regulation is investigated for almost similar power system models. The compendium for this work is as following: (i) modelling of wind generator‐based microgrid using MATLAB simulink library, (ii) designing of STATCOM current controller with PI controller, (iii) gain constants estimation using classical, GA and PSO algorithm through a developed m codes and their interfacing with proposed simulink model, (v) dynamic frequency responses for proposed grid connected microgrid during starting and load perturbations, (vi) verification of system performance with the help of obtained real and reactive power management between STATCOM and grid, and (vii) validation of results with available literature.

 
more » « less
Award ID(s):
1711951
NSF-PAR ID:
10444648
Author(s) / Creator(s):
 ;  ;  ;  ;  
Publisher / Repository:
Wiley Blackwell (John Wiley & Sons)
Date Published:
Journal Name:
International Journal of Circuit Theory and Applications
Volume:
50
Issue:
9
ISSN:
0098-9886
Page Range / eLocation ID:
p. 3231-3250
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. null (Ed.)
    With more and more renewable energy resources integrated into the power grid, the system is losing inertia because power electronics-based generators do not provide natural inertia. The low inertia will cause the microgrid to be more sensitive to disturbance and thus a small load change may result in a severe deviation in frequency. Based on the basic VSG algorithm, which is to mimic the characteristic of the traditional synchronous generator, the frequency can be controlled to a stable value faster and more smoothly when there is a fluctuation in the PV power generation and/or load change. However, characteristic of the VSG depends on the system structure in consideration of multiple generations, such as Synchronous Generator (SG), PV and Battery Energy Storage System (BESS), which greatly increases the complexity of applying VSG in practical power system. Furthermore, with BESS-VSG, Maximum Power Point (MPP) operation of PV is guaranteed. In addition, an adaptive VSG method is developed for a microgrid system, and the corresponding simulation in Matlab/Simulink shows the effectiveness of the adaptive VSG method. 
    more » « less
  2. null (Ed.)
    In this paper, we introduce a distributed secondary voltage and frequency control scheme for an islanded ac microgrid under event-triggered communication. An integral type event-triggered mechanism is proposed by which each distributed generator (DG) periodically checks its triggering condition and determines whether to update its control inputs and broadcast its states to neighboring DGs. In contrast to existing event-triggered strategies on secondary control of microgrids, the proposed event-triggered mechanism is able to handle the consensus problem in case of asynchronous communication. Under the proposed sampled-data based event-triggered mechanism, DGs do not need to be synchronized to a common clock and each individual DG checks its triggering condition periodically, relying on its own clock. Furthermore, the proposed method efficiently reduces communication rate. We provide sufficient conditions under which microgrid's frequency and a critical bus voltage asymptotically converge to the nominal frequency and voltage, respectively. Finally, effectiveness of our proposed method is verified by testing different scenarios on an islanded ac microgrid benchmark in the MATLAB/Simulink environment as well as a hardware-in-the-loop (HIL) platform, where the physical system is modeled in the Opal-RT and the cyber system is realized in Raspberry Pis. 
    more » « less
  3. A high frequency solid-state transformer (SST) proposed by FREEDM centre is an interesting alternative to conventional distribution transformer in microgrids as it supports additional functionalities such as active-reactive power flow control, fault current limitation and voltage regulation. This paper proposes a dynamic phasor based robust control of SST through the modular control of each stage. The control problem is formulated in frequency domain by representing the system states with time varying Fourier coefficients or dynamic phasors (DP). This formulation transforms the oscillating waveforms of ac circuits to constant or slowly varying variables, hence allow the use of PI controller to track the sinusoidal references. For rectifier and inverter stages of SST, dq transformation is applied on DP which facilitates the design of PI controller to smoothen out the ripples in the output voltage waveform. The controller gains are tuned to reject input and load disturbances and attenuate measurement noise using loop shaping and pole assignment technique. The robustness of the controller is assured analytically against parametric uncertainties using small gain theorem. Simulation results are provided to support the proposed control scheme. Hardwarein- Loop (HIL) simulation is carried out on critical stages using Opal-RT and dSPACE simulators to confirm the effectiveness of the proposed scheme. 
    more » « less
  4. null (Ed.)
    The primary purpose of this paper is to obtain accurate analytical expressions of the dual active bridge (DAB) converter under the three-degree of freedom control technique. This technique, known as triple phase-shift (TPS) modulation, is utilized for the efficiency optimization of different operating zones and modes of the DAB. Three operating zones and modes have been retained to analyze the converter. Depending on the operating regions and due to the high nonlinearity of the obtained expressions, two optimization techniques have been used. The offline particle swarm optimization (PSO) method is utilized in local optimization (LO) and results in a numerical value. The Lagrange Multiplier (LM) is utilized in global optimization (GO) and results in a closed form expression. In the case of LO, the optimal duty cycles that minimize the power loss are not the optimal values for the minimum root-mean-square (RMS) current or peak current stress. Conversely, in the case of GO, the optimal duty cycles minimize the RMS, peak current and power loss at the same time for the entire power range. Detailed analyses and simulation results from MATLAB/Simulink are given to prove the effectiveness of the proposed method. 
    more » « less
  5. null (Ed.)
    High integration of renewable energy resources, such as wind turbines, to the power grid decreases the power system inertia. To improve the frequency response of a low-inertia system, virtual inertia approach can be used. This letter proposes a control method to decrease the frequency transients and restore frequency to its nominal value. A wind turbine usually works based on maximum power point tracking (MPPT) curves to achieve the maximum power. In this letter, the proposed controller uses a non-MPPT method to leave power for frequency regulation during transients. Moreover, it uses a washout filter-based method to remove the steady-state error in the frequency. Simulation results in the PSCAD environment validate the improved performance of the proposed method during load changes by comparing it with the MPPT and non-MPPT methods. 
    more » « less