Title: Thermal Impacts of Air Cavities Associated with Insulated Panels Deployed for Exterior Building Envelope Assemblies
This paper presents a comprehensive investigation to evaluate the impacts of air cavities between existing walls and insulated panels on the overall R-values of the retrofitted building envelope systems, addressing a key challenge in exterior envelope retrofitting. The effects of several factors are considered including the air cavity thickness (ranging from 0.1 cm to 5 cm), airflow velocity (varying between 0.1 m/s and 1 m/s), and surface emissivity (set between 0.1 and 0.9), in addition to the thickness of the insulated panels (ranging from 1 cm to 7 cm). It is found that any increase in the air cavity thickness increases the overall R-values of the building envelope assemblies when air is trapped within the sealed cavity. However, when air convection is prevalent, the overall R-value of the retrofitted walls decreases with any increase in air velocity and air cavity thickness. For sealed air cavities, the analysis results show a 9% improvement in R-value of the retrofitted walls. However, the R-value of retrofitted walls with unsealed air cavities can degrade by 76% and 81% for natural and forced air flows, respectively. Emissivity adjustment is found to be the most effective in improving the thermal performance of building envelopes with sealed air cavities, increasing the R-value of retrofitted walls by 13.6% when reduced from 0.9 to 0.1.  more » « less
Award ID(s):
2113907
PAR ID:
10620574
Author(s) / Creator(s):
;
Editor(s):
MDPI
Publisher / Repository:
MDPI
Date Published:
Journal Name:
Energies
Volume:
18
Issue:
13
ISSN:
1996-1073
Page Range / eLocation ID:
3573
Subject(s) / Keyword(s):
Air Cavity Thickness Air Velocity, Building Envelope Emissivity Insulation Thermal Resistance.
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. null (Ed.)
    During this study, full-size wood composite sandwich panels, 1.2 m by 2.4 m (4 ft by 8 ft), with a biaxial corrugated core were evaluated as a building construction material. Considering the applications of this new building material, including roof, floor, and wall paneling, sandwich panels with one and two corrugated core(s) were fabricated and experimentally evaluated. Since primary loads applied on these sandwich panels during their service life are live load, snow load, wind, and gravity loads, their bending and compression behavior were investigated. To improve the thermal characteristics, the cavities within the sandwich panels created by the corrugated geometry of the core were filled with a closed-cell foam. The R-values of the sandwich panels were measured to evaluate their energy performance. Comparison of the weight indicated that fabrication of a corrugated panel needs 74% less strands and, as a result, less resin compared to a strand-based composite panel, such as oriented strand board (OSB), of the same size and same density. Bending results revealed that one-layer core sandwich panels with floor applications under a 4.79 kPa (100 psf) bending load are able to meet the smallest deflection limit of L/360 when the span length (L) is 137.16 cm (54 in) or less. The ultimate capacity of two-layered core sandwich panels as a wall member was 94% and 158% higher than the traditional walls with studs under bending and axial compressive loads, respectively. Two-layered core sandwich panels also showed a higher ultimate capacity compared to structural insulated panels (SIP), at 470% and 235% more in bending and axial compression, respectively. Furthermore, normalized R-values, the thermal resistance, of these sandwich panels, even with the presence of thermal bridging due to the core geometry, was about 114% and 109% higher than plywood and oriented strand board, respectively. 
    more » « less
  2. MDPI (Ed.)
    This paper provides an analysis of challenges and available solutions for exterior insulated panels suitable for deep energy retrofits of existing building envelopes. The analysis covers a review of available technologies that provide flexible retrofit insulated panels suitable for multiple climates and building typologies. Moreover, the paper proposes a new design for insulated retrofit panels that account for the majority of identified technical risks including cost, architectural diversity, climate variations, structural concerns, moisture resilience, air sealing, and water sealing. Additionally, the proposed design can be easily installed with minimal disruption to the occupants. A series of parametric and optimization analyses is carried out to identify the optimal design specifications for insulated panels suitable for deep retrofits of existing US housing stocks. The analysis results show that the optimal design criteria for the insulated panels can reduce heating and cooling energy consumption by up to 80% and HVAC capacities by 70%. Moreover, the results indicate that these insulated panels are highly cost effective for retrofitting US housing units located in cold climates. 
    more » « less
  3. The drag reduction technique involving air cavities under ship hulls is a promising energy-saving technology. Understanding the air cavity dynamics in unsteady conditions and developing methods for the air cavity system optimization are critically important for practical implementation of this technology. In this study, a potential-flow theory is applied for modeling the air cavities under solid walls in water flow with fluctuating pressure. The present modeling approach incorporates detachment of macroscopic air pockets from the cavity tail. For specific configurations considered in this article, it is found that a change of the rate of air supply into the cavity can partly mitigate degradation of the overall power savings by the air cavity system in unsteady conditions. 
    more » « less
  4. ABSTRACT We study the evolution of eccentricity and inclination of massive planets in low-density cavities of protoplanetary discs using three-dimensional (3D) simulations. When the planet’s orbit is aligned with the equatorial plane of the disc, the eccentricity increases to high values of 0.7–0.9 due to the resonant interaction with the inner parts of the disc. For planets on inclined orbits, the eccentricity increases due to the Kozai–Lidov mechanism, where the disc acts as an external massive body, which perturbs the planet’s orbit. At small inclination angles, $${\lesssim}30^\circ$$, the resonant interaction with the inner disc strongly contributes to the eccentricity growth, while at larger angles, eccentricity growth is mainly due to the Kozai–Lidov mechanism. We conclude that planets inside low-density cavities tend to acquire high eccentricity if favourable conditions give sufficient time for growth. The final value of the planet’s eccentricity after the disc dispersal depends on the planet’s mass and the properties of the cavity and protoplanetary disc. 
    more » « less
  5. This research introduces a novel lyophilized hydrogel for double-skin envelope (DSE) integration as a dynamic louver system to provide dehumidification of moisture, daylighting modulation, and recuperation of water condensate. The work links empirical experiments for thermal, optical, and sorption properties of the hygrothermal materials alongside system scale analytical models to inform energy and water conservation measures. The system scale analyses are conducted with LBNL WINDOW7 in combination with numerical analytical models, in addition to select computational fluid dynamic (CFD) studies for development of louver geometries to optimize sorption effectiveness in the DSE cavity airstream. Effective heat transfer and visible transmittance values for the dynamic states of the DSE hygrothermal louver system are then linked to building scale analyses in the Rhino- Grasshopper platform using the Honeybee plug-in to run EnergyPlus. The dynamic state envelope system is assessed through annual integration modeling for hothumid climate conditions. The work introduces new aspects in simulation modeling with integration of the standard mechanical air-handling system functions to be coupled with multi-state dynamic properties for the envelope system in building scale analyses. A sorption coefficient is identified for analytical modeling of the DSE hygrothermal louver cavity thermodynamics. The work also integrates a new calculation tool in the simulation platform for evaluating potential water recuperation 
    more » « less