Title: Experimental Characterization of the Transient Response of Air/Water Crossflow Heat Exchangers for Data Center Cooling Systems
Data Center hybrid air/liquid cooling systems such as rear door heat exchangers, overhead and in row cooling systems enable localized, on-demand cooling, or “smart cooling.” At the heart of all hybrid cooling systems is an air to liquid cross flow heat exchanger that regulates the amount of cooling delivered by the system by modulating the liquid or air flows and/or temperatures. Due the central role that the heat exchanger plays in the system response, understanding the transient response of the heat exchanger is crucial for the precise control of hybrid cooling system. This paper reports on the transient experimental characterization of heat exchangers used in data centers applications. An experimental rig designed to introduce controlled transient perturbations in temperature and flow on the inlet air and liquid flow streams of a 12 in. × 12 in. heat exchanger test core is discussed. The conditioned air is delivered to the test core by a suction wind tunnel with upstream air heaters and a frequency variable axial blower to allow the control of air flow rate and bulk temperature. The conditioned water is delivered to the test core by a water delivery system consisting of two separate water circuits, one delivering cold water, and the other hot water. By switching from one circuit to the other or mixing water from both circuits, the rig is capable of generating step, ramp and frequency perturbations in water temperature at constant flow or step, ramp or frequency perturbations in water flow at constant temperature or combinations of temperature and water flow perturbations. Experimental data are presented for a 12×12 heat exchanger core with a single liquid pass under different transient perturbations  more » « less
Award ID(s):
1738782
PAR ID:
10058024
Author(s) / Creator(s):
;
Date Published:
Journal Name:
ASME 2015 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems collocated with the ASME 2015 13th International Conference on Nanochannels, Microchannels, and Minichannels
Page Range / eLocation ID:
V001T09A021
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. The most common approach to air cooling of data centers involves the pressurization of the plenum beneath the raised floor and delivery of air flow to racks via perforated floor tiles. This cooling approach is thermodynamically inefficient due in large part to the pressure losses through the tiles. Furthermore, it is difficult to control flow at the aisle and rack level since the flow source is centralized rather than distributed. Distributed cooling systems are more closely coupled to the heat generating racks. In overhead cooling systems, one can distribute flow to distinct aisles by placing the air mover and water cooled heat exchanger directly above an aisle. Two arrangements are possible: (i.) placing the air mover and heat exchanger above the cold aisle and forcing downward flow of cooled air into the cold aisle (Overhead Downward Flow (ODF)), or (ii.) placing the air mover and heat exchanger above the hot aisle and forcing heated air upwards from the hot aisle through the water cooled heat exchanger (Overhead Upward Flow (OUF)). This study focuses on the steady and transient behavior of overhead cooling systems in both ODF and OUF configurations and compares their cooling effectiveness and energy efficiency. The flow and heat transfer inside the servers and heat exchangers are modeled using physics based approaches that result in differential equation based mathematical descriptions. These models are programmed in the MATLAB™ language and embedded within a CFD computational environment (using the commercial code FLUENT™) that computes the steady or instantaneous airflow distribution. The complete computational model is able to simulate the complete flow and thermal field in the airside, the instantaneous temperatures within and pressure drops through the servers, and the instantaneous temperatures within and pressure drops through the overhead cooling system. Instantaneous overall energy consumption (1st Law) and exergy destruction (2nd Law) were used to quantify overall energy efficiency and to identify inefficiencies within the two systems. The server cooling effectiveness, based on an effectiveness-NTU model for the servers, was used to assess the cooling effectiveness of the two overhead cooling approaches 
    more » « less
  2. The constant increase in data center computational and processing requirements has led to increases in the IT equipment power demand and cooling challenges of highdensity (HD) data centers. As a solution to this, the hybrid and liquid systems are widely used as part of HD data centers thermal management solutions. This study presents an experimental based investigation and analysis of the transient thermal performance of a stand-alone server cabinet. The total heat load of the cabinet is controllable remotely and a rear door heat exchanger is attached with controllable water flow rate. The cooling performances of two different failure scenarios are investigated. One is in the water chiller and another is in the water pump for the Rear Door Heat eXchanger (RDHX). In addition, the study reports the impact of each scenario on the IT equipment thermal response and on the cabinet outlet temperature using a mobile temperature and velocity mesh (MTVM) experimental tool. Furthermore, this study also addresses and characterizes the heat exchanger cooling performance during both scenarios. 
    more » « less
  3. null (Ed.)
    An in-rack cooling system connected to an external vapor recompression loop can be an economical solution to harness waste heat recovery in data centers. Validated subsystem-level models of the thermosyphon cooling and recompression loops (evaporator, heat exchangers, compressor, etc.) are needed to predict overall system performance and to perform design optimization based on the operating conditions. This paper specifically focuses on the model of the evaporator, which is a finned-tube heat exchanger incorporated in a thermosyphon cooling loop. The fin-pack is divided into individual segments to analyze the refrigerant and air side heat transfer characteristics. Refrigerant flow in the tubes is modeled as 1-D flow scheme with transport equations solved on a staggered grid. The air side is modeled using differential equations to represent the air temperature and humidity ratio and to predict if moisture removal will occur, in which case the airside heat transfer coefficient is suitably reduced. The louver fins are modeled as individual hexagons and are treated in conjunction with the tube walls. A segment-by-segment approach is utilized for each tube and the heat exchanger geometry is subsequently evaluated from one end to the other, with air property changes considered for each subsequent row of tubes. Model predictions of stream outlet temperature and pressure, refrigerant outlet vapor quality and heat exchanger duty show good agreement when compared against a commercial software. 
    more » « less
  4. Abstract

    An in-rack cooling system connected to an external vapor recompression loop can be an economical solution to harness waste heat recovery in data centers. Validated subsystem-level models of the thermosyphon cooling and recompression loops (evaporator, heat exchangers, compressor, etc.) are needed to predict overall system performance and to perform design optimization based on the operating conditions. This paper specifically focuses on the model of the evaporator, which is a finned-tube heat exchanger incorporated in a thermosyphon cooling loop. The fin-pack is divided into individual segments to analyze the refrigerant and air side heat transfer characteristics. Refrigerant flow in the tubes is modeled as 1-D flow scheme with transport equations solved on a staggered grid. The air side is modeled using differential equations to represent the air temperature and humidity ratio and to predict if moisture removal will occur, in which case the airside heat transfer coefficient is suitably reduced. The louver fins are modeled as individual hexagons and are treated in conjunction with the tube walls. A segment-by-segment approach is utilized for each tube and the heat exchanger geometry is subsequently evaluated from one end to the other, with air property changes considered for each subsequent row of tubes. Model predictions of stream outlet temperature and pressure, refrigerant outlet vapor quality and heat exchanger duty show good agreement when compared against a commercial software.

     
    more » « less
  5. The ability of traditional room-conditioning systems to accommodate expanding information technology loads is limited in contemporary data centers (DCs), where the storage, storing, and processing of data have grown quickly as a result of evolving technological trends and rising demand for online services, which has led to an increase in the amount of waste heat generated by IT equipment. Through the implementation of hybrid air and liquid cooling technologies, targeted, on-demand cooling is made possible by employing a variety of techniques, which include but are not limited to in-row, overhead, and rear door heat exchanger (HX) cooling systems. One of the most common liquid cooling techniques will be examined in this study based on different conditions for high-power density racks (+50 kW). This paper investigates the cooling performance of a liquid-to-air in-row coolant distribution unit (CDU) in test racks containing seven thermal test vehicles (TTVs) under various conditions, focusing on cooling capacity and HX effectiveness under different supply air temperatures (SAT). This test rig has the necessary instruments to monitor and analyze the experiments on both the liquid coolant and the air sides. Moreover, another experiment is conducted to assess the performance of the CDU that runs under different control fan schemes, as well as how the change of the control type will affect the supply fluid temperature and the TTV case temperatures at 10%, 50%, and 100% of the total power. Finally, suggestions for the best control fan scheme to use for these systems and units are provided at the conclusion of the study.

     
    more » « less