skip to main content


Title: The Effectiveness of Data Center Overhead Cooling in Steady and Transient Scenarios: Comparison of Downward Flow to a Cold Aisle Versus Upward Flow From a Hot Aisle
The most common approach to air cooling of data centers involves the pressurization of the plenum beneath the raised floor and delivery of air flow to racks via perforated floor tiles. This cooling approach is thermodynamically inefficient due in large part to the pressure losses through the tiles. Furthermore, it is difficult to control flow at the aisle and rack level since the flow source is centralized rather than distributed. Distributed cooling systems are more closely coupled to the heat generating racks. In overhead cooling systems, one can distribute flow to distinct aisles by placing the air mover and water cooled heat exchanger directly above an aisle. Two arrangements are possible: (i.) placing the air mover and heat exchanger above the cold aisle and forcing downward flow of cooled air into the cold aisle (Overhead Downward Flow (ODF)), or (ii.) placing the air mover and heat exchanger above the hot aisle and forcing heated air upwards from the hot aisle through the water cooled heat exchanger (Overhead Upward Flow (OUF)). This study focuses on the steady and transient behavior of overhead cooling systems in both ODF and OUF configurations and compares their cooling effectiveness and energy efficiency. The flow and heat transfer inside the servers and heat exchangers are modeled using physics based approaches that result in differential equation based mathematical descriptions. These models are programmed in the MATLAB™ language and embedded within a CFD computational environment (using the commercial code FLUENT™) that computes the steady or instantaneous airflow distribution. The complete computational model is able to simulate the complete flow and thermal field in the airside, the instantaneous temperatures within and pressure drops through the servers, and the instantaneous temperatures within and pressure drops through the overhead cooling system. Instantaneous overall energy consumption (1st Law) and exergy destruction (2nd Law) were used to quantify overall energy efficiency and to identify inefficiencies within the two systems. The server cooling effectiveness, based on an effectiveness-NTU model for the servers, was used to assess the cooling effectiveness of the two overhead cooling approaches  more » « less
Award ID(s):
1738782
NSF-PAR ID:
10058026
Author(s) / Creator(s):
; ;
Date Published:
Journal Name:
ASME 2015 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems collocated with the ASME 2015 13th International Conference on Nanochannels, Microchannels, and Minichannels
Page Range / eLocation ID:
V001T09A023
Format(s):
Medium: X
Sponsoring Org:
National Science Foundation
More Like this
  1. Forecasting data center cooling demand remains a primary thermal management challenge in an increasingly larger global energy-consuming industry. This paper proposes a dynamic modeling approach to evaluate two different strategies for delivering cold air into a data center room. The common cooling method provides air through perforated floor tiles by means of a centralized distribution system, hindering flow management at the aisle level. We propose an idealized system such that five overhead heat exchangers are located above the aisle and handle the entire server cooling demand. In one case, the overhead heat exchangers force the airflow downwards into the aisle (Overhead Downward Flow (ODF)); in the other case, the flow is forced to move upwards (Overhead Upward Flow (OUF)). A complete fluid dynamic, heat transfer, and thermodynamic analysis is proposed to model the system’s thermal performance under both steady state and transient conditions. Inside the servers and heat exchangers, the flow and heat transfer processes are modeled using a set of differential equations solved in MATLAB™. This solution is coupled with ANSYS-Fluent™, which computes the three-dimensional velocity, temperature, and turbulence on the Airside. The two approaches proposed (ODF and OUF) are evaluated and compared by estimating their cooling effectiveness and the local Entropy Generation. The latter allows identifying the zones within the room responsible for increasing the inefficiencies (irreversibilities) of the system. Both approaches demonstrated similar performance, with a small advantage shown by OUF. The results of this investigation demonstrated a promising approach of data center on-demand cooling scenarios. 
    more » « less
  2. Data centers house a variety of compute, storage, network IT hardware where equipment reliability is of utmost importance. Heat generated by the IT equipment can substantially reduce its service life if Tjmax, maximum temperature that the microelectronic device tolerates to guarantee reliable operation, is exceeded. Hence, data center rooms are bound to maintain continuous conditioning of the cooling medium becoming large energy consumers. The objective of this work is to introduce and evaluate a new end-of-aisle cooling design which consists of three cooling configurations. The key objectives of close-coupled cooling are to enable a controlled cooling of the IT equipment, flexible as well as modular design, and containment of hot air exhaust from the cold air. The thermal performance of the proposed solution is evaluated using CFD modeling. A computational model of a small size data center room has been developed. Larger axial fans are selected and placed at rack-level which constitute the rack-fan wall design. The model consists of 10 electronic racks each dissipating a heat load of 8kw. The room is modeled to be hot aisle containment i.e. the hot air exhaust exiting for each row is contained and directed within a specific volume. Each rack has passive IT with no server fans and the servers are cooled by means of rack fan wall. The cold aisle is separated with hot aisle by means of banks of heat exchangers placed on the either sides of the aisle containment. Based on the placement of rack fans, the design is divided to three sub designs — case 1: passive heat exchangers with rack fan walls; case 2: active heat exchangers (HXs coupled with fans) with rack fan walls; case 3: active heat exchangers (hxs coupled with fans) with no rack fans. The cooling performance is calculated based on the thermal and flow parameters obtained for all three configurations. The computational data obtained has shown that the case 1 is used only for lower system resistance IT. However, case 2 and Case 3 can handle denser IT systems. Case 3 is the design that can consume lower fan energy as well as handle denser IT systems. The paper also discusses the cooling behavior of each type of design. 
    more » « less
  3. Most of the thermal management technologies concentrate on managing airflow to achieve the desired server inlet temperature (supply air operating set point) and not to manage/improve the amount of cool air (CFM) that each computer rack (i.e. IT servers) should receive in order to remove the produced heat. However, airflow is equally important for quantifying adequate cooling to IT equipment, but it is more challenging to obtain a uniform airflow distribution at the inlet of computer racks. Therefore, as a potential option for improving airflow distribution is to eliminate the sources of non-uniformities such as maldistribution of under-floor plenum pressure field caused by vortices. Numerous researchers focus on the adverse effects of under-floor blockages. This study focused to numerically investigate the positive impact of selectively placed obstructions (on-purpose air-directors); referred as partitions; Quantitative and qualitative analysis of underfloor plenum pressure field, perforated tiles airflow rate and racks inlet temperature with and without partitions using two Computational Fluid Dynamics (CFD) models, which were built using Future Facilities 6SigmaRoom CFD tool. First, a simple data center model was used to quantify the partitions benefits for two different systems; Hot Aisle Containment (HAC) compared to an open configuration. Second, the investigation was expanded using a physics-based experimentally validated CFD model of medium size data center (more complicated data center geometry) to compare different types of proposed partitions. Both models results showed that partition type I (partitions height of $\frac{2}{3}$ of plenum depth measured from the subfloor) eliminates the presence of vortices in the under-floor plenum and hence, more uniform pressure differential across the perforated tiles that drives more uniform airflow rates. In addition, the influence of proposed partitions on the rack inlet temperature was reported through a comparison between open versus hot aisle containment. The results showed that the partitions have a minor effect on the rack inlet temperature for the hot aisle containment system. However, the partitions significantly improve the tiles flowrate. On the other hand, for the open system, the presence of partitions has improved the tiles airflow rate, rack inlet temperature and hence eliminate the hot spots formation at computer rack inlet 
    more » « less
  4. Optimizing data centers for energy efficiency plays a key role in the successful operation of modern data centers. One important factor is the proper management of airflow. In most air-cooled data centers, the required airflow for cooling of IT equipment is supplied from a raised floor to server racks through perforated tiles. In recent years, different approaches have been implemented to increase the efficiency of air delivery through tiles such as the use of directional tiles, adding understructure scoops or using air dampers [1]. Because the IT load of each rack in the data center is constantly changing due to the processing demands of the IT hardware at a given time, simultaneous manual tuning of the airflow at the panel level is impossible or at least impractical. The amount of airflow delivered to the Cold Aisle Containment (CAC) can be adjusted using Variable Airflow Panels (Dampers) that can be controlled remotely. In this study, we design and optimize a fuzzy control system to control the open area ratio of air dampers in order to adjust the local airflow rate in the ES2 data center. 
    more » « less
  5. There are various designs for segregating hot and cold air in data centers such as cold aisle containment (CAC), hot aisle containment (HAC), and chimney exhaust rack. These containment systems have different characteristics and impose various conditions on the information technology equipment (ITE). One common issue in HAC systems is the pressure buildup inside the HAC (known as backpressure). Backpressure also can be present in CAC systems in case of airflow imbalances. Hot air recirculation, limited cooling airflow rate in servers, and reversed flow through ITE with weaker fan systems (e.g. network switches) are some known consequences of backpressure. Currently there is a lack of experimental data on the interdependency between overall performance of ITE and its internal design when a backpressure is imposed on ITE. In this paper, three commercial 2-rack unit (RU) servers with different internal designs from various generations and performance levels are tested and analyzed under various environmental conditions. Smoke tests and thermal imaging are implemented to study the airflow patterns inside the tested equipment. In addition, the impact leak of hot air into ITE on the fan speed and the power consumption of ITE is studied. Furthermore, the cause of the discrepancy between measured inlet temperatures by internal intelligent platform management interface (IPMI) and external sensors is investigated. It is found that arrangement of fans, segregation of space upstream and downstream of fans, leakage paths, location of sensors of baseboard management controller (BMC) and presence of backpressure can have a significant impact on ITE power and cooling efficiency. 
    more » « less